Premium Choice Low Profile Humidity Sensor Module Manual

5
Floor Area
(sq. ft.²)
Number of Bedrooms
1 2 3 4 5
CFM Requirements
<500 30 38 45 53 60
501-1000 45 53 60 68 75
1001-1500 60 68 75 83 90
1501-2000 75 83 90 98 105
2001-2500 90 98 105 113 120
2501-3000 105 113 120 128 135
3001-3500 120 128 135 143 150
3501-4000 135 143 150 158 165
4001-4500 150 158 165 173 180
Local Exhaust Requirement
A local mechanical exhaust system shall be
installed in each kitchen and bathroom:
Kitchens: 100 CFM intermittent or 5 ACH
continuous (based on kitchen volume)
Bathrooms: 50 CFM intermittent or 20 CFM
continuous
Use a PC Premium Choice Bath Fan in each
bathroom to meet the ASHRAE 62.2 Local
Exhaust Requirement. Please note each
bathroom fan counts towards meeting the
ASHRAE 62.2 Whole Building Requirement.
Whole Building Requirement
Required ventilation is based on the size of the
house and number of expected occupants.
1. Calculation:
Minimum Required CFM = 0.03A +
7.5(Number of bedrooms +1)
If the number of occupants exceeds the
assumed 2 persons for the rst bedroom
and 1 for each additional room, increase
the ventilation rate as follows: Number of
additional occupants x 7.5 CFM
2. Use the Whole Building Ventilation
Requirements CFM chart from the ASHRAE
62.2 Standard:
ASHRAE 62.2
ASHRAE 62.2
The ASHRAE 62.2 Standard applies to all residential spaces that are “intended for human
occupancy” in single family homes and multi-family structures up to three stories. These spaces
include living rooms, bedrooms, kitchens, bathrooms, hallways, closets, store rooms, laundry
rooms, garages, and basements.
There are two components of the ASHRAE 62.2 standard that relate to ventilation fans: Whole
Building Ventilation & Local Exhaust.