User Manual

Delete. To delete an entry from the DNP table, select the entry in the table and then press the
Delete button.
Output Delay. This value defines the amount of time (in milliseconds) between transmitting DNP
packets to the SpeedNet Radio’s serial interface after they are received over the wireless
interface. This feature has been added to accommodate legacy equipment that cannot receive
data packets as quickly as the SpeedNet Radio can deliver them. The default value is 80
milliseconds.
Input Timeout. This value defines the amount of time (in milliseconds) that the serial interface
will wait before sending a packet after data is received. The default value is 60 milliseconds.
SpeedNet Radios include a feature that allows multiple SCADA masters using the same SCADA address
to be connected to a single SpeedNet Radio. When using this feature, the connected SpeedNet Radio
continually monitors DNP traffic. In the case of multiple SCADA masters using the same SCADA
address, the SpeedNet Radio will consider the master to be the device that sent the most recent data
packet. If the active SCADA master experiences a failure, the SpeedNet Radio will automatically forward
packets from the backup SCADA master.
Configuration of this feature is very simple. When building the SCADA table, each SCADA master will
use the same SCADA Address. The IP address will be unique for each SCADA master.
For example, assume there are two SCADA master devices, one with an IP address of 192.168.200.20
(primary SCADA master) and one with an IP address of 192.168.200.30 (secondary SCADA master). To
create the table entry for the primary SCADA master, enter 192.168.200.20 into the IP Address field.
Enter 25 into the SCADA address field. To create the table entry for the secondary SCADA master, enter
192.168.200.30 into the IP Address field. Enter 25 into the SCADA address field.
Repeater Serial Mode
The SpeedNet Radio Repeater serial port mode provides the same configuration parameters as the DNP
serial port mode – see above for details. As shown in the figure below, one additional parameter is
available when the Repeater serial mode is selected.
Enable Battery Testing. Provides the ability for SpeedNet Radios to occasionally test the status
of a connected backup battery system. When this feature is enabled the results of battery tests
can be seen on the Batt Status Tab of the Statistics page.
Serial Port Tab