Operating instructions
Page 8 
    Zeus Mini Instructions 
Example: 
Flue system consists of 9m of 80mm air intake pipe with 3 x 90 bends and 6m of exhaust pipe with 2 x 90 
bends. 
Component Resistances: 
Component  Resistance  Quantity  Total 
80mm Intake pipe  2.3  9  20.7 
90˚ air intake bend  5  3  15 
80mm Flue pipe  3  6  18 
90˚ Flue bend  6.5  3  19.5 
73.2 
Total Flue Resistance 
In this case the total resistance of the 
system is less than 100. The flue de-
sign is acceptable. 
Care should be taken to insulate the 
exhaust flue pipe to ensure that con-
densation is not possible. 