Overview of Primary Product

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
runtalnorthamerica.com
Runtal Radiators have been tested to ISO standards #3147-3150
for panel radiation. The ratings shown in the tables are based on
a 65ºF (18ºC) entering air temperature, and include a 15% heat
effect factor.
To determine the rating of a radiator at an average water
temperature (AWT) other than what is shown in the tables,
multiply the rating at 215ºF (102ºC) by the appropriate factor
in the table below.
RF-1 2.8 2.0 550 390 220
RF-2 5.7 2.0 870 620 350
RF-3 8.6 2.0 1120 790 460
RF-4 11.5 2.0 1360 960 550
RF-5 14.4 2.0 1720 1210 700
RF-6 17.3 2.0 1990 1400 800
RF-7 20.2 2.0 2150 1510 880
RF-8 23.1 2.0 2390 1680 970
RF-9 26.0 2.0 2530 1780 1020
RF-10 29.0 2.0 2660 1880 1080
R2F-1 2.8 5.0 980 690 400
R2F-2 5.7 5.0 1590 1120 640
R2F-3 8.6 5.0 2020 1420 820
R2F-4 11.5 5.0 2420 1700 980
R2F-5 14.4 5.0 3100 2180 1250
R2F-6 17.3 5.0 3470 2450 1400
R3F-1 2.8 5.0 1300 920 530
R3F-2 5.7 5.0 2020 1420 820
R3F-3 8.6 5.0 2580 1810 1040
R3F-4 11.5 5.0 3090 2170 1250
R3F-5 14.4 5.0 3790 2670 1530
R3F-6 17.3 5.0 4270 3000 1720
Model Unit HeigHt MoUnting deptH 215ºF 180ºF 140ºF
inCHeS inCHeS BtUH/Ft BtUH/Ft BtUH/Ft
R-1 2.8 2.0 230 160 90
R-2 5.7 2.0 420 300 170
R-3 8.6 2.0 620 440 250
R-4 11.5 2.0 820 580 330
R-5 14.4 2.0 1020 720 410
R-6 17.3 2.0 1220 860 500
R-7 20.2 2.0 1430 1010 580
R-8 23.1 2.0 1640 1160 660
R-9 26.0 2.0 1850 1300 750
R-10 29.0 2.0 2060 1450 830
Temperature 215˚F 200˚F 190˚F 180˚F 170˚F 160˚F 150˚F 140˚F 130˚F 120˚F 110˚F
Correction Factor 1.0 .87 .79 .70 .63 .55 .51 .40 .33 .27 .21
LENGTHS AVAILABLE IN 2” INCREMENTS FROM 20” TO 29'6".
CorreCtion FaCtor at average Heating water teMperatUre
R MODELS
RF MODELS
R2F MODELS
R3F MODELS
R3F
R3F
Heating Capacities