Installation Rules:
1. Unit is intended for installation in Restricted Access Location only.
2. Unit shall be installed on/above concrete or other non combustible surface only.
3. The minimum distance between the BS antennas and the public zone is at least 1
meter
4. The unit shall be installed at least 5 meters above the ground level
5. When unit is installed outdoors length of exposed outdoor wiring shall not exceed
130ft (46meters)
6. Unit earthing screw terminal shall be permanently connected to protective earth in
building installation in accordance with applicable national code and regulations.
7. The screen of the coaxial cables (connections to outdoor antennas) shall be
permanently connected to protective earth in building installation.
8. In Finland, Norway and Sweden unit shall be installed in a Restricted Access
Location where equipotential bonding has been applied (e.g. telecommunication
center).
9. Unit power line 48VDC shall be protected by 2-pole circuit breaker, suitably certified
in accordance with applicable national code and regulations, and rated not more
than 2A.
10. Unit shall be installed only by qualified service person.