Specifications

77
XD
V10
N
ominal Capacity, 60 Hz1 10 kW / 2.8 Ton
N
ominal Capacity, 50 Hz1 8 kW / 2.3 Ton
N
ominal Airflow, 60 Hz 1000 CFM (1700 m
3
/h)
N
ominal Airflow, 50 Hz 830 CFM (1410 m
3
/h)
In
put Voltage 120 V, 1 ph, 60 Hz
230 V
, 1 ph, 50/60 Hz
Full load amps 2A @ 120V, 1ph, 60 Hz
1A @ 230V
, 1ph, 50 Hz
Audible Noise, 60 Hz / 50 Hz 78 dBa / 73 dBa Sound Power
Height, module only 14” (355 mm)
Width 23” (581 mm)
Depth 29.5”-39.5” (749-1003 mm)
Weight, empty 77 lbs (35 kg)
Options Quick Connect Couplings (for Flexible Piping)
Condensate Detection (dry contacts)
1 N
ominal Capacity Rating is @ 55°F (13°C) Entering Fluid Temperature and 98°F (37°C) Entering Air Temperature.
Max capacity 60Hz: XDV10 - 11.8kW @ 106 F (41 C)
Max capacity 50Hz: XDV10 - 11.8kW @ 116 F (47 C)
Specifications
Liebert XDV Related Products
Liebert Nform
A simple to use monitoring and
communications software solution
th
a
t c
omb
ine
s f
ull-scale monitoring
with cost-effective deployment
through the use of the existing
network infrastructure.
L
iebert IntelliSlot Web/485 card
with a
d
a
p
t
e
r
Enables the Network and Building
Management Systems that monitor
y
o
ur c
om
puting, communication
and facility infrastructure to also
m
onit
or y
o
ur Li
ebert cooling
equipment through your existing
network.
Liebert XDC
Ex
tr
e
m
e D
e
nsity Heat Rejection
Specifically designed to support the
Liebert XDV and XDH high-density
c
oolin
g system that removes the
heat from the critical space.
Liebert Universal Monitor
This all-purpose, simple to use
m
onitoring panel features multi-
sensing, remote monitoring and
remote control capabilities.
Liebert Liqui-tect
®
Leak
Detection Systems
Provide quick sensing, accurate
reporting and precise location of
le
aks below the floor or above the
ceiling in critical facilities, allowing
you to find and correct a leak before
moisture can damage computers,
wir
in
g c
onnections or other
s
e
nsitive electronics.