Specifications
61
A
ccuVar TVSS Technical Specifications
Maximum Continuous
Operating Voltage (MCOV) 120V 125%, all others 115%
F
ault Current Rating (AIC) 200 kAIC
Operating Frequency Range 47 – 63 Hz
C
onnection Parallel (10-14 AWG)
50 EMI/RFI Attenuation 10 kHz-100MHz
(60 dB – O
ptional) (60 dB – Optional)
Response Time <0.5 ns
O
perating Humidity 0% to 95%
S
tatus Indication LEDs, Audible Alarm (Standard), Dry Contacts (Optional)
Certifications UL 1449 & 1283, CSA, CE,
NEMA L
S-1, ISO 9001 NEMA LS-1, ISO 9002
Enclosure NEMA 4X
W
arranty 10 Years parts
Shipping Weight 8 lb.
UL 1449 second edition clamping data
Voltage
L-N L-G L-L N-G
120/208 400 400 800 400
120/240 400 400 800 400
240 X 800 800 X
277/480 800 800 1500 800
36/600 1200 1200 2000 1200
480 X 1500 1500 X
600 X 2000 2000 X
EMI/RFI Noise Rejection
Single Unit Fr
equency System Installation
120/208 400 400
120/240 400 400
240 X 800
277/480 800 800
36/600 1200 1200
480 X 1500
600 X 2000
L
ife Cycle Surge Testing -
10kA
, 20kV, IEEE Cat. C3
Unit Per Mode(L-N/L-G/N-G) Per Phase
ACV 6,000 / 6,000 / 6,000 12,000
All 8,000 / 8,000 / 8,000 16,000
Nominal (L-G)
Voltage Codes
120 120V
208 208V
230 230V
240 240V
277 277V
346 346V
480 480V
600 600V
Source Configuration
- 1 Phase L-N 2w + gnd
(must put “-“ in part number)
- 1 Phase L-L 2w + gnd
(must put “-“ in part number)
S Split Phase 3w + gnd
Y 3 Phase Wye 4w + gnd
D 3 Phase Delta 3w + gnd
H 3 Phase Delta Hi-leg 4w+ gnd
Option Codes
R Standard Options – (Red & Green LED’s,
Audible Alarm wit hEnable/Disable Feature)
RE Standard Options +
Enhanced EMI/RFI Filtering
RK Standard Options + Alarm Relay Contacts
RKE Standard Options + Enhanced EMI/RFI
Filtering & Alarm Relay Contacts
Model/Surge Current
ACV
ACCUVAR
65kA
Per Mode
ALL
ACCUVAR II
80kA
Per Mode