Specifications

54
Liebert FPC Power Distribution Unit
Specifications
F
eature APC
In
fraStruXure
L
iebert FPC PDI
P
owerpack
PDU
M
GE Power
M
anagement
Module
Monitoring
Local and remote monitoring is
standard. Liebert Distribution
M
onitoring (optional) can adapt
m
onitoring to include any
combination of panelboard main
breaker, branch breaker, sub-feed
breakers and / or output breaker.
Branch circuit
monitoring optional
(local an
d remote)
Local and remote
branch circuit
m
onitoring optional.
L
ocal monitoring
optional.
Branch circuit monitoring
optional. Advanced
m
onitoring (advanced
m
ulti-function meter
options that encompass
additional metering and
monitoring features) is
o
ptional.
Unlike competitive products that are limited to two
alarms and branch circuit monitoring only, Liebert’s
m
onitoring with optional Liebert Distribution
M
onitoring provides over 500 monitoring and alarm
points per panelboard and has dozens of monitoring
parameters to choose from. Liebert’s comprehensive
monitoring increases the likelihood that users are
ale
rted of potential problems before those problems
can a
ffect the connected equipment, thereby
r
educing the chance of costly unplanned downtime.
Panelboard
Sp
ace
Two panelboards for 15-125 kVA.
A
dditional panelboard space, 4
ins
tead of 2, for 50-125kVA.
U
nique in-line panelboards
provide additional wiring space
(50% more s
pace than our old
product) in the wiring area. 42
pole
s in a single row versus side-
by-side.
Two panelboards Two panelboards
s
tandard. Two
a
dditional
p
anelboards
optional.
(33”x38”x69”) 2
panelboards.
41”W with 4
panelboards
42"x27x"72" 2 panel boards.
72"W with 4 panel boards
One size
(34”x34”x69”)
Two panelboards,
A
dditional panelboards
ar
e optional by adding
d
istribution cabinet.
The Liebert FPC has more panelboard options, for 50
kV
A and greater. Since panelboards provide
e
xpansion opportunities so there are always enough
b
ranch circuits, the FPC has the greatest flexibility to
expand as power densities increase, while keeping
cos
ts low.
The Liebert FPC’s two sizes provide IT professionals
with more flexibility than competitors’ cabinets as
users configure their spaces.
Sizes
WxDxH
19”x38.5”x78.5”
and
47”x38.5”x78.5”
29”x36”x81”
U
nited
P
ower
PDM
Remote
monitoring is
s
tandard.
Br
anch circuit
monitoring is
optional.
Two
p
anelboards,
A
dditional
p
anelboards are
optional by
add
ing
distribution
ca
binet.
Th
e Liebert Advantage
Competitive Comparison
Liebert FPC 15-125 KVA 150 KVA
Power Rating
Rating (kVA) 15, 30, 50, 75, 100, 125 150
Rating (kW) 15, 30, 50, 75, 100, 125 150
Input AC Specifications
Input Voltage 480 480
Input Voltage Range -13% to +6% -13% to +6%
In
put Current (Amps) 19-156 185
Frequency (Hz) 60 60
F
requency Range +/-0.5Hz +/-0.5Hz
Phase 3 3
Power Factor 0.75 to 1.0 0.75 to 1.0
Surge Protection ANSI/IEEE C62.41 Category B3 ANSI/IEEE C62.41 Category B3
Input Circuit Breaker (Amps) 25-200 250
Input Connections Junction Box w/10 ft field wired cable Junction Box w/10 ft field wired cable
O
u
tp
u
t A
C Sp
ecifications
P
ane
lbo
ar
ds 2 4
N
ominal Voltage 208/120 208/120
Branch Circuit Breakers 84 168
Frequency (Hz) 60 60
Efficiency 96.5 to 98% 96.5 to 98%
O
u
tput Waveform Sine Wave Sine Wave
Crest Factor Up to 3.5 Up to 3.5
Distortion 0.5% Max Additive 0.5% Max Additive
T
r
ans
f
o
r
mer Specifications
T
y
pe
Double Shielded Double Shielded
Windings Copper Copper
NEMA S
t
an
d
ar
d
TP1
TP1
Temperature Rise 150°C 150°C
Impedance 4.5% to 4.7% 4.5% to 4.7%
T
aps 6 (-10% to +5%) 6 (-10% to +5%)
Overload Protection 2 Sensors per winding (180°C & 200°C) 2 Sensors per winding (180°C & 200°C)