Specifications

P
OWER DISTRIBUTION
GXT 2-6000RT208
Model Number Amp Rating Input Power Connection Output Power Connection
P
D-HDWR 30 No Bypass Hardwire Terminals Hardwire Terminals
P
D-HDWR-MBS 30 With Bypass Hardwire Terminals Hardwire Terminals
PD-001 30 With Bypass L14-30P (1) L6-30R,(1) L14-30R,
(4) 5-15/20R T
-slot
P
D-002 30 With Bypass L14-30P (2) L6-20R, (2) 5-15/20R T-slot
PD-003 30 With Bypass L14-30P (2) L6-30R,
(4) 5-15/20R T-slot
P
D-004 30 With Bypass L14-30P (4) EN60320 / C19
P
D-005 30 With Bypass L14-30P (4) L5-20R,
(2) L5-30R
P
D-006 30 With Bypass L14-30P (4) L5-20R, (2) L6-30R
P
D-007 30 With Bypass L14-30P (4) L6-20R
GX
T 2-6000RTL630
M
odel Number Amp Rating Input Power Connection Output Power Connection
P
D-L630 30 L6-30P (2) L6-30R, (2) L6-20R
GXT 2-10000RT208
M
odel Number Amp Rating Input Power Connection Output Power Connection
P
D-101 50 Hard Wired (8) 5-15/20R T-slot, (2) L6-30R
PD-102
50 Hard Wired (4) 5-15/20R T-slot, (4) L6-20R
PD
-103 50 Hard Wired (4) 5-15/20R T-slot, (4) L6-30R
P
D-104 50 Hard Wired
(4) 5-20R T
-slot, (2) L6-30R, (2) L6-20R
PD-105 50 Hard Wired
(4) 5-20R T-slot, (2) L6-30R, (2) L5-20R
42
Liebert GXT UPS
Specifications
Total Runtime with Internal
and Extended Battery
Cabinets/Full Load
BATTERY CABINETS
UPS Model Runtime with Internal Extended Battery
Batteries @ Full Load Cabinet P/N Voltage One Cabinet Two Cabinets
GXT2-500RT120 28 minutes GXT2-48VBATT 48 VDC 115 min. 231 min.
GXT2-700RT120 17 minutes GXT2-48VBATT 48 VDC 68 min. 136 min.
GXT2-1000RT120 11 minutes GXT2-48VBATT 48 VDC 44 min. 88 min.
GXT2-1500RT120 7 minutes GXT2-48VBATT 48 VDC 28 min. 56 min.
GXT2-2000RT120 6 minutes GXT2-48VBATT 48 VDC 18 min. 42 min.
GXT2-3000RT120 5 minutes GXT2-72VBATT 72 VDC 20 min. 40 min.
GXT2-2700RT208 5 minutes GXT2-72VBATT 72 VDC 20 min. 40 min.
GX
T2-6000RTL630 7 minutes GXT2-240VBATTUL 240 VDC 21 min. 38 min.
GXT2-6000RT208 5 minutes GXT2-144VBATT 144 VDC 14 min. 25 min.
GX
T2-10000R
T208
6 min
u
t
e
s GXT2-288VBATT 288 VDC 17 min. 28 min.
P
ARALLEL C
APABILITY
GXT2-10000RT208
Model Description
GXT2-PP20KRT208 Paralleling POD maximum (3) GXT2-10000RT208 connection for 20kVA capacity plus 10kVA
r
edun
d
anc
y (r
equires (1) paralleling cable p/n GXT2-20KPC-6 for connection to each
GX
T2-10000R
T208)
GXT2-20KPC-6 Paralleling cable, approximately 6 feet long
SYSTEM CONFIGURATION
Capacity / Redundancy GXT2-10000RT208 GXT2-288RTBKIT GXT2-PP20KRT208 GXT2-20KPC-6 PD-201
10kVA / 10kVA 2* 4* 1* 2* 1
20kVA / - 2* 4* 1* 2* 1
20kV
A / 10kVA 3* 6* 1* 3* 1
* Required Paralleling Components