Specifications
40
Liebert GXT UPS
S
pecifications
M
odel Number GXT2-500RT120 GXT2-700RT120 GXT2-1000RT120 GXT2-1500RT120
Model Rating VA/W 500VA/350W 700VA/ 490W 1000VA / 700W 1500VA / 1050W
Dim
ensions: in (mm) 3.5 x 21.5 x 17 in. 3.5 x 21.5 x 17 in. 3.5 x 21.5 x 17 in. 3.5 x 21.5 x 17 in.
W x D x H (89 x 546 x 432 mm) (89 x 546 x 432 mm) (89 x 546 x 432 mm) (89 x 546 x 432 mm)
W
eight: lbs. (kg) 49 lbs. (22 kg) 49 lbs. (22 kg) 50 lbs. (23 kg) 51 lbs. (23 kg)
Input AC Parameters
V
oltage Range 120 VAC nominal, (60 to 140VAC Variable based upon output load)
F
requency 40 - 70 Hz; Auto Sensing
Input Power Cord 6 ft. attached, w/ NEMA 6 ft. attached, w/ NEMA 10 ft. attached, w/ NEMA 10 ft. attached, w/ NEMA
5-15 p
lug 5-15 plug 5-15 plug 5-15 plug
Output AC Parameters
O
utput Receptacles (6) NEMA 5-15R (6) NEMA 5-15R (6) NEMA 5-15R (6) NEMA 5-15R
Voltage 100/110/115/120/127 (user configurable) VAC; ±3%
Frequency 50 Hz or 60 Hz
Waveform Sinewave
Typical Battery Backup Time
F
ull Load 28 minutes 17 minutes 11 minutes 7 minutes
Half L
oad 66 minutes 44 minutes 25 minutes 20 minutes
R
echarge Time 5 Hours to 95% capacity after full discharge into 100% load
Agency
Safety UL 1778; c-UL Listed
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE 587 Category A & B
Transportation ISTA Procedure 1A
Model Number GXT2-2000RT120 GXT2-2700RT208 GXT2-3000RT120
Model Rating VA/W 2000VA / 1400W 2700VA/1890W 3000VA / 2100W
Dimensions: in (mm) 3.5 x 21.5 x 17 in. 3.5 x 24.2 x 17 in. 3.5 x 24.2 x 17 in.
W x D x H (89 x 546 x 432 mm) (89 x 615 x 432 mm) (89 x 615 x 432 mm)
Weight: lbs. (kg) 54 lbs. (24kg) 75.2 (34.1) 69 lbs. (31kg)
Input AC Parameters
Voltage Range 120 VAC nominal, 208 VAC nominal, 120 VAC nominal,
(60 to 140VAC Variable based upon output load) (119 to 280VAC Variable based upon output load) (60 to 140VAC Variable based upon output load)
F
r
eq
u
ency 40 - 70 Hz; Auto Sensing 40 - 70 Hz; Auto Sensing 40 - 70 Hz; Auto Sensing
Input Power Cord 10 ft. attached, w/ NEMA 10 ft. attached w/ NEMA L6-20 plug 10 ft. attached, w/ NEMA
5-20 plug 5-15 plug L5-30 plug
Output AC Parameters
Output Receptacles (6) 5-20 T-Slot (2) NEMA L6-15R (6) NEMA 5-15R
receptacles (1) NEMA L6-20R (1) NEMA L5-30R on 12” cord
V
o
lt
age 100/110/115/120/127 (user configurable) VAC; ±3% 200/208/220/230/240 (user configurable) VAC; ±3% 100/110/115/120/127 (user configurable) VAC; ±3%
Frequency 50 Hz or 60 Hz 50 Hz or 60 Hz 50 Hz or 60 Hz
Waveform Sinewave Sinewave Sinewave
T
ypi
c
al B
a
tt
ery Backup Time
Full Load 6 minutes 5 minutes 5 minutes
Half Load 14 minutes 16 minutes 16 minutes
Recharge Time 5 Hours to 95% capacity after full discharge into 100% load
Agency
Safety UL 1778; c-UL Listed
RFI/EM
I
FCC Part 15, Subpart B, Class A
Surge Immunity IEEE 587 Category A & B
Transportation ISTA Procedure 1A