Specifications

36
Liebert PowerSure PSI UPS
M
odel Number PS1000RT2-120 PS1440RT2-120 PS1920RT2-120 PS2200RT2-120 PS3000RT2-120
M
odel Number with Liebert IntelliSlot
W
eb/SNMP Card Installed
PS1000R
T2-120W PS1440RT2-120W PS1920RT2-120W PS2200RT2-120W PS3000RT2-120W
P
ower Rating, VA/W 1000VA/750W 1440VA/1080W 1920VA/1500W 2200VA/1650W 3000VA/2250W
Dimensions, W x D x H, in (mm)
Unit 3.43 x 22 x 17 3.43 x 22 x 17 3.43 x 24.1 x 17 3.43 x 24.1 x 17 3.43 x 24.1 x 17
(87 x 557 x 430) (87 x 557 x 430) (87 x 612 x 430) (87 x 612 x 430) (87 x 612 x 430)
Weight, lbs (kg)
Unit 61.7(28.0) 68.2(31.0) 77.0 (35.0) 77.0 (35.0) 81.6 (37.0)
In
put AC Parameters
Sur
ge Protection 570J
V
oltage Range Without
B
attery Operation
78V
AC - 150VAC, configurable
Frequency Range 45 - 65 Hz (±0.1 Hz)
Input Power Cord 10 ft. (3m) attached, 10 ft. (3m) attached, 10 ft. (3m), attached, 10 ft. (3m) attached, 10 ft. (3m) attached,
w/NEMA 5-15 P w/NEMA 5-15 P NEMA 5-20 P w/NEMA L5-30 P w/NEMA L5-30 P
Output AC Parameters
O
utput Receptacles (8) NEMA 5-15 R (8) NEMA 5-15 R (6) NEMA 5-15 R (6) NEMA 5-15 R (4) NEMA 5-15 R
2) NEMA 5-20 R
(2) NEMA 5-20 R (2) NEMA 5-20 R
T-Slot, accepts 15APlug T-Slot, accepts 15APlug (1) NEMA L5-30 R
T-Slot, accepts 15APlug
Voltage (Normal mode) 110 / 120 / 127 VAC (configurable) ±10%
Voltage (Battery Mode) 110 / 120 / 127 VAC (configurable);
±5% before low battery warning; ±8% after low battery warning
Transfer Time 4-6 ms typical
Waveform Sinewave
Frequency (Normal Mode) 45 - 65 Hz (±0.1 Hz)
Frequency (Battery Mode) 50 or 60 Hz (±5%); auto sensing
Battery Parameters
Load% PS1000RT2-120(W) PS1440RT2-120(W) PS1920RT2-120(W) PS2200RT2-120(W) PS3000RT2-120(W)
Internal Battery Runtime
20% 65 min. 45 min. 52 min. 47 min. 47 min.
40% 37 min. 24 min. 25 min. 23 min. 22 min.
60% 24 min. 14 min. 15 min. 13 min. 14 min.
80% 16 min. 9 min. 10 min. 8 min. 9 min.
100% 11 min. 5 min. 6 min. 5 min. 6 min.
Recharge Time 4 hours to 90% of rated capacity, after full discharge into resistive load
External Battery Cabinet PS2-48VBATT PS2-48VBATT PS2-72VBATT PS2-72VBATT PS2-72VBATT
Model Number
Internal Battery Runtime + 1 External Battery Cabinet
50% 119 min. 72 min. 105 min. 99 min. 67 min.
100%
46 min
.
30 min
.
43 min. 40 min. 29 min.
Internal Battery Runtime + 2 External Battery Cabinets
50%
209 min
. 133 min. 163 min. 150 min. 129 min.
100%
98 min. 56 min. 89 min. 77 min. 52 min.
Internal Battery Runtime + 3 External Battery Cabinets
50% 274 min. 209 min. 237 min. 222 min. 168 min.
100% 136 min. 95 min. 128 min. 120 min. 88 min.
Internal Battery Runtime + 4 External Battery Cabinets
50% 305 min. 257 min. 281 min. 274 min. 222 min.
100% 188 min. 125 min. 150 min. 144 min. 118 min.
Environmental
O
perating Temperature +32°F to + 104°F (0°C to + 40°C)
Storage Temperature +5°F to + 104°F (-15°C to + 40°C)
Relative Humidity 0% to 95%, non-condensing
Operating Altitude Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Audible Noise <40 dBA, internal fan(s) off <40 dBA, internal fan(s) off
<50 dB
A
, in
ternal fan(s) on <60 dBA, internal fan(s) on
Agency
S
afety UL 1778, c-UL Listed
IEEE 587, Category A
Emis
si
ons (RFI/EM
I)
FCC P
ar
t 15, C
l
a
s
s B FCC Part 15, Class A
Transportation ISTA Procedure 1A Certification
Specifications
Surge Immunity