1-Phase CX1 Technical Data
H. CX1 TECHNICAL DATA
H.1 1-Phase
Model
kW (Btu/
hr)
Unit
Voltage
Gas Group
Supply
Wire Size ***
Unit
Current
Max. Circuit
Fuse*
Cabinet
Length
Temperature
Code
IIB +
H2
IIB IIC
V
w/o
T'stat
w/
T'stat
w/o
T'stat
w/
T'stat
AWG A A
in (mm)
CX1-120160-012-T3
1.2 (4095) 120
12 10.0 15 31.3 (796) T3 (200)
CX1-120160-018-T3
1.8 (6142) 120
12 15.0 20 31.3 (796) T3 (200)
CX1-208160-012-T3 1.2 (4095) 208
12 5.8 15 31.3 (796) T3 (200)
CX1-208160-018-T3 1.8 (6142) 208
12 8.7 15 31.3 (796) T3 (200)
CX1-208160-036-T3** 3.6 (12284) 208
12 17.3 25 49.5 (1256) T3 (200)
CX1-208160-048-T2A 4.8 (16378) 208 N/A
8 23.1 30 49.5 (1256) T2A (280)
CX1-208160-050-T3
5.0 (17060)
208
N/A
8
24.0
30
71.8 (1823)
T3 (200)
CX1-208160-076-T2A 7.6 (25932) 208 N/A N/A 8 36.5 50 59.5 (1511) T2A (280)
CX1-240160-012-T3 1.2 (4095) 240
12 5.0 15 31.3 (796) T3 (200)
CX1-240160-018-T3 1.8 (6142) 240
12 7.5 15 31.3 (796) T3 (200)
CX1-240160-036-T3** 3.6 (12284) 240
12 15.0 20 49.5 (1256) T3 (200)
CX1-240160-048-T2A 4.8 (16378) 240
10 20.0 25 49.5 (1256) T2A (280)
CX1-240160-050-T3 5.0 (17060) 240
8 20.8 30 71.8 (1823) T3 (200)
CX1-240160-076-T2A 7.6 (25932) 240 N/A N/A 8 31.7 40 59.5 (1511) T2A (280)
CX1-277160-012-T3 1.2 (4095) 277
12 4.3 15 31.3 (796) T3 (200)
CX1-277160-018-T3 1.8 (6142) 277
12 6.5 15 31.3 (796) T3 (200)
CX1-277160-036-T3** 3.6 (12284) 277
12 13.0 20 49.5 (1256) T3 (200)
CX1-277160-048-T2A 4.8 (16378) 277
12 17.3 25 49.5 (1256) T2A (280)
CX1-277160-050-T3 5.0 (17060) 277
8 18.1 25 71.8 (1823) T3 (200)
CX1-277160-076-T2A 7.6 (25932) 277 N/A N/A 8 27.4 35 59.5 (1511) T2A (280)
CX1-380160-0075-T3 0.75 (2560) 380
12 2.0 15 31.3 (796) T3 (200)
CX1-380160-0113-T3 1.13 (3856) 380
12 3.0 15 31.3 (796) T3 (200)
CX1-380160-012-T3 1.2 (4095) 380
12 3.2 15 31.3 (796) T3 (200)
CX1-380160-018-T3 1.8 (6142) 380
12 4.7 15 31.3 (796) T3 (200)
CX1-380160-0226-T2A 2.26 (7711) 380
12 5.9 15 31.3 (796) T2A (280)
CX1-380160-0301-T3 3.01 (10271) 380
12 7.9 15 49.5 (1256) T3 (200)
CX1-380160-0313-T3 3.13 (10680) 380
12 8.2 15 71.8 (1823) T3 (200)
CX1-380160-036-T3** 3.6 (12284) 380
12 9.5 15 49.5 (1256) T3 (200)
CX1-380160-0476-T2A 4.76 (16241) 380
10 12.5 20 59.5 (1511) T2A (280)
CX1-380160-048-T2A 4.8 (16378) 380
10 12.6 20 49.5 (1256) T2A (280)
CX1-380160-050-T3 5.0 (17060) 380
10 13.2 20 71.8 (1823) T3 (200)
CX1-380160-0626-T2A 62.6 (21360) 380
N/A 8 16.5 25 71.8 (1823) T2A (280)
CX1-380160-076-T2A 7.6 (25932) 380
N/A 8 20.0 25 59.5 (1511) T2A (280)
CX1-380160-100-T2A 10.0 (34121) 380 N/A N/A 8 26.3 35 71.8 (1823) T2A (280)
CX1-400160-0083-T3 0.83 (2832) 400
12 2.1 15 31.3 (796) T3 (200)
CX1-400160-012-T3 1.2 (4095) 400
12 3.0 15 31.3 (796) T3 (200)
Notes
* Or equivalent breaker as per local electrical inspection authority
requirements.
*** Ensure supply wire size adheres to applicable local and national
electrical codes.
1. Heater is functioning normally if, at rated voltage, the current draw is
within 10% of the value in this table.
2. Operation at lower voltages that rated will result in reduced output
and current draw.
3. Actual Output (kW) = [(Supply Voltage)
2
÷ (Rated Voltage)
2
] × Rated
Unit Wattage (kW)]
4. Add suffix "T" for optional built-in thermostat. Thermostat not
available on IIB+H2 models.