User manual

Seite 81 von 128
AUTONOMY TIME Minutes (at 50% / 100% effective power load)
Standard (internal battery) 17 / 6 - -
+ 1 Batterypack - 18 / 6 12 / 5
+ 2 Batteriepacks - 51 / 19 31 / 16
+ 3 Batteriepacks - 93 / 36 55 / 26
+ 4 Batteriepacks - 121 / 53 73 / 40
INTERFACE, SOFTWARE
RS-232 interface Yes
Dry contacts (battery capac-
ity high/low, shutdown)
Yes
Network management card,
basic
Optional
Network management card,
professional
Optional
USB-adaptor Optional
DataWatch software Included in scope of supply
Table 12: Electrical specifications
11.3 Ambient conditions
MODEL
XANTO RT
1000
XANTO RT
2000
XANTO RT
3000
Operating temperature (°C) 0 - 40
Storage temperature (°C) -25 to +55
Relative humidity (%) 5 - 95%, no condensation
Cooling
Active cooling, 2 internal fans, air inlet on
front
Altitude
1500 - 3000m, power derating of 1% per
additional 100m
Operating noise (dB) 43 45 45
Table 13: Ambient conditions