460MXE Gateway User Guide
Trademarks CompactLogix, ControlLogix, & PLC-5 are registered trademarks of Rockwell Automation, Inc. EtherNet/IP is a trademark of the Open DeviceNet Vendors Association (ODVA). MicroLogix, RSLogix 500, and SLC are trademarks of Rockwell Automation, Inc. Microsoft, Windows, and Internet Explorer are registered trademarks of Microsoft Corporation. All other trademarks and registered trademarks are the property of their holders. Limited Warranty Real Time Automation, Inc.
460 Gateway Device Line 460MXE Overview The 460MXE gateway device seamlessly connects power and energy data between one or more Eaton Power Meters and a BACnet/IP Client or Ethernet/IP Client or DeviceNet Master. By following this guide, you will be able to configure the 460MXE gateway for basic operation. You will set the device’s network settings and parameters to the proper configuration for initial operation and physically place the device in the network.
60 Gateway Device Line 460MXE Required Tools and Data You will need the following tools: ♦ The 460MXE Gateway ♦ The provided CD-ROM ♦ A Working PC (Windows based) ♦ The Supplied Ethernet crossover cable ♦ A 7-30 VDC power source (T-strip) You will also need to verify the following Modbus Slave Settings: ♦ Data Timeout ♦ Baud Rate ♦ Parity ♦ Data Bits ♦ Stop Bits Real Time Automation, Inc.
460 Gateway Device Line 460MXE Port Connections (BACnet/IP / Modbus and Ethernet/IP / Modbus) The factory default port settings on the 460MXE gateway are for Port 0 (T-strip) to be set for RS485 including power (Pin 5). Port 1 (DB9) is set to RS232 by default. If these default port are not compatible with your equipment they can be configured differently. For specific jumper settings refer to the end of this manual, appendix A.
460 Gateway Device Line 460MXE Port Connections (DeviceNet / Modbus) The factory default port settings on the 460MXE gateway are for Port 0 (T-strip) to be set for CAN while Port 1 (DB9) is set to RS485 by default. If these default port are not compatible with your equipment they can be configured differently. For specific jumper settings refer to the end of this manual, appendix A. For assistance changing port configurations contact our customer support department. Real Time Automation, Inc.
460 Gateway Device Line 460MXE Accessing the Main Page Before you can configure the gateway itself you must configure the network settings to connect the gateway. The following steps will connect the gateway properly. 1) Connect a 7-30 VDC power source to the device. 2) Using the crossover cable (supplied) connect the device to the PC. (NOTE: If you are connecting to the device via a hub or a switch use a standard Ethernet cable.) 3) Insert the provided CD-ROM. NOTE 4) Run the IPSetup.
460 Gateway Device Line 460MXE Error: Main Page Does Not Launch If the Main Page does not launch the IP address is most likely incorrect. Correct the IP address and try again. If you do not know the IP address use the following procedure: 1) Open an MS-DOS Command Prompt. 2) Type ipconfig and press enter. 3) Note the IP address. (The previous example was 192.168.0.1) 4) To test the communication between the PC and the unit, type ping (###.###.###.###) in the prompt and press enter. The (###.###.###.
460 Gateway Device Line 460MXE Choosing a Protocol Now that the device is on the network you will need to select what protocol you are connecting to (BACnet/IP or Ethernet/IP or DeviceNet). 1) If you would like to change the device description, on the main page, in the Description row, click Edit. Otherwise, skip to step 4. 2) Type the desired description into the text box. 3) Click Save.
460 Gateway Device Line 460MXE Modbus RTU Master Settings Now that the device is on the network you will configure the device settings. As a reminder you will need to know the baud rate, parity, data bits and stop bit settings of your Modbus slave device in order to complete device configuration. 1) If you would like to change the device description, on the main page, in the Description row, click Edit. Otherwise, skip to step 4. 2) Type the desired description into the text box. 3) Click Save.
460 Gateway Device Line 460MXE Configuring External Master Modules 1) From the Main page click Edit in the Client Module Configuration row. 2) There are four options for external devices: ♦ Eaton IQ 250/260 Power Meter ♦ Eaton IQ 130, 140, 150 ♦ Eaton Power Xpert 2000 ♦ Eaton Power Xpert 4000, 6000, 8000 ♦ Add Generic Remote Modbus RTU Slave (Continued on page 10) Real Time Automation, Inc.
460 Gateway Device Line 460MXE 3) Selecting any of the first four devices will install the device with preset Data In settings. The device Slave address and Data Out parameters will still need to be configured. 4) To add a generic Modbus slave device click on the Add Generic Remote Modbus Slave Device button. 5) Enter a name for the device in the Device Label field to help distinguish between multiple devices. 6) In the Slave address enter the address that corresponds to your Modbus Slave Device.
460 Gateway Device Line 460MXE Scan List Settings 1) Data in values are values received from the Modbus slave device which are considered inputs to BACnet. 2) Data out values are the values sent from the BACnet device to the Modbus slave. 3) The Point Type/Data Type values will match those of the Modbus slave device. 4) Length is the number of data types to be read. (It is not the number of registers) 5) Click Save.
460 Gateway Device Line 460MXE BACnet IP Server Settings 1) Scroll down to the BACnet Server row and click Edit. Verify that the Enabled box is checked. 2) Enter the Device Instance that corresponds with your Modbus Slave device/s. 3) In the Device Name field enter a unique name for the device. 4) The Description and Locations fields are optional. Filling in the fields is recommended to identify the device on a network. 5) Beneath # of Objects to Expose, values should all be kept as zero.
460 Gateway Device Line 460MXE Ethernet/IP Server 1) For the Data Out column do the same as Step 8 except use the correct Output Instance Number, Length in bytes, and Required Pack Interval in milliseconds. 2) Click Save when configuration is complete. You must restart the 460 device in order for the data to be updated. Real Time Automation, Inc.
460 Gateway Device Line 460MXE DeviceNet Slave Settings Now that the device is on the network, you will configure the device settings. As a reminder, you will need to know the mode, baud rate, parity, data and stop bit settings of your device in order to complete device configuration. 1) If you would like to change the device description, on the main page, in the Description row, click Edit. Otherwise, skip to step 4. 2) Type the desired description into the text box. 3) Click Save.
460 Gateway Device Line 460MXE Application Parameters 1) Next Application Parameters click Edit. 2) 460MXE Mapping will display the connection between the tags / file names in your PLC to the BACnet/IP Object within your Client. Real Time Automation, Inc.
460 Gateway Device Line 460MXE Verifying Application Parameters 1) On the Main Page click on the Status and Summary button located on the left hand side of the screen. 2) The 460MXE Device Summary and Status page will be shown. 3) The device drop down menu allows you to switch between the different devices and display their status. 4) Under Show you can choose to show only values that are greater than zero. Summary can be left unchecked as that feature has not been implemented yet.
460 Gateway Device Line 460MXE Validating Gateway Communication If the Timeout counter or the Error counter are incrementing or a status of Enabled Not Connected, refer to the Troubleshooting Tops to help get the device up and running. Real Time Automation, Inc.
460 Gateway Device Line 460MXE Configuring Multiple Devices If you are configuring multiple devices the same way, you can repeat the configuration by saving your work into a file. To do so, follow these steps. 1) From the Main Page, click the Utilities button. 2) Click Save Configuration to File. 3) Click Save. 4) Browse to the location you want to save the file. 5) Click OK. 6) Remove the first device. 7) Repeat the network configuration section to connect the next device.
460 Gateway Device Line 460MXE Completing the Installation Now that the 460MXE gateway is configured properly you must place the device in the network. The following instructions will tell you how to take the device from the configuration area to the shop floor or other operating environment. 1) Disconnect the crossover cable and power supply from the device. 2) Move the device to its intended location. 3) For Bacnet/IP or Ethernet/IP, follow steps 4-6. For DeviceNet, skip to step 7.
460 Gateway Device Line 460MXE Jumper Configurations To change port settings on the 460 EDX Gateway use the following steps: 1) No cables should be connected to the Gateway unit. If this unit has been in use and you are making a change, disconnect the power cable and any communications cables from the Gateway unit. 2) Remove the two small Phillips-head screws from each long side of the Gateway unit. 3) Remove the green T-Strip connector. Slide the cover off towards the ports.
460 Gateway Device Line 460MXE NC= No connection Port 0 (T-Strip) CAN 1 2 3 4 5 Pin Setting GND CANL SHIELD CANH PWR Port 1 (DB-9) RS485 1 2 3 4 5 6 7 8 9 Pin Setting NC TX- NC NC GND NC TX+ NC NC NC= No connection Port 0 (T-Strip) CAN 1 2 3 Pin Setting GND CANL SHIELD CANH PWR Port 1 (DB-9) RS232 1 2 3 4 5 6 7 8 9 Pin Setting NC RX TX NC GND NC NC NC NC Real Time Automation, Inc.
Real Time Automation, Inc. 150 South Sunny Slope Road Suite 130 Brookfield WI 53005 Toll free 1-800-249-1612 Local (262) 439-4999 www.rtaautomation.com support@rtaautomation.