User guide

Diagnostics Modbus RTU Slave
LED Status:
1. Good Communication (Solid Green) The gateway is connected to a Modbus RTU Master and
communicating as expected.
2. Not Connected (Flashing Green) The gateway has never been connected to a Modbus RTU
Master.
3. Fatal Error (Solid Red) The port configured does not match the port configured within the
Modbus RTU configuration page.
4. Connection Timeout (Flashing Red) The gateway has lost a connection to the Modbus RTU
Master.
Variables:
1. FC01 Read Coil Status Modbus Function Code 1: Number of Read Coil Status requests received.
2. FC02 Read Input Status Modbus Function Code 2: Number of Read Input Status requests
received.
3. FC03 Read Holding Registers Modbus Function Code 3: Number of Read Holding Registers
requests received.
4. FC04 Read Input Registers Modbus Function Code 4: Number of Read Input Registers requests
received.
5. FC05 Force Single Coil Modbus Function Code 5: Number of Write Coil Status requests
received.
6. FC06 Preset Single Register Modbus Function Code 6: Number of Write Holding Register
requests received.
7. FC15 Force Multiple Coils Modbus Function Code 15: Number of Write multiple Coil Status
requests received.
8. FC16 Preset Multiple Registers Modbus Function Code 16: Number of Write multiple Holding
Register requests received.
9. FC23 Read/Write 4X Register Modbus Function Code 23: Number of Read/Write Holding
Registers requests received.
10. Successful Responses Received Total number of Read/Write messages sent by the gateway.
11. Error Responses Received = Total number of Read/Write errors sent by the gateway.
12. Timeouts Total number of Inactivity Timeouts that have occurred.
Real Time Automation, Inc. 52 1-800-249-1612