User guide

Recoverable Faults: 0x00FF0000 (bit 16-23)3
rd
byte
Hex: Bit Position: Decimal: Explanation:
0x01 16 65,536 recoverable fault - timed out
0x02 17 131,072 recoverable fault - Slave err
Non-Recoverable Faults 0xFF000000 (bit 24-31)4
th
byte
Hex: Bit Position: Decimal: Explanation:
0x01 24 16,777,216 nonrecoverable fault
task fatal err
0x02 25 33,554,432 nonrecoverable fault
config missing
0x04 26 67,108,864 nonrecoverable fault
bad hardware port
0x08 27 134,217,728 nonrecoverable fault
config err
0x10 28 268,435,456 Configuration Mode
0x20 29 536,870,912 No Ethernet Cable Plugged In
For this example the MC Status is mapped to a PLC tag called MC_Status
Example: MC Status is 0x00010041 (65601 decimal), here is the break down, we know that bytes 1 and 3
are being used, so here is the break down,
Common Status:
Hex: Bit: Decimal: Explanation:
0x01 0(on) 1 if we are a Master/Client
0x40 6(on) 64
recoverable fault
Recoverable Faults:
Hex: Bit: Decimal: Explanation:
0x01 16 65,536 recoverable fault timed
Total: 0x010041 65,601
Real Time Automation, Inc. 32 1-800-249-1612