User manual

Default IP Address – 192.168.0.100
Figure 2-52 External Device Configuration screen
8. Enter the Device Address. Enter the registers and program tags for each data type in this
Device Buffer.
9. Select Save. The Master and Client Module External Device List re-displays with the
information entered for that Device Buffer. To add another Device Buffer, click on the
Add Remote BACnet/IP Server button and then edit that buffer’s settings.
10. When you have finished enabling Device Buffers for the BACnet/IP Client, click on .
The RTA 460 Gateway Main Page displays.
Main
BACnet/IPServerconfiguration
If your version of the 460 Gateway requires your gateway to act as a BACnet/IP Server, use the
following steps to configure the gateway. At least two Communication Modules must be
configured.
1. Click on next to the
Selected Communication Modules on the RTA 460 Gateway
Main Page. See Figure 2-2.
The Communication Module Configuration screen displays. See Figure 2-54.
Edit
Note: The Edit buttons are grayed out when the task applies to a different 460
Gateway version than you purchased. Please contact Real Time
460 Gateway User Manual Page 41