Default IP Address – 192.168.0.100
Figure 2-24 Modbus TCP Client data selections
11. When you have finished editing device buffers for the Modbus TCP Client, click on .
The RTA 460 Gateway Main Page displays.
Main
ModbusTCPServerconfiguration
If your version of the 460 Gateway requires your gateway to act as a Modbus TCP Server, use
the following steps to configure the gateway. At least two Communication Modules must be
configured.
1. Click on next to the Selected Communication Modules on the RTA 460 Gateway
Main Page. See Figure 2-2.
The Communication Module Configuration screen displays. See Figure 2-25.
Edit
Note: The Edit buttons are grayed out when the task applies to a different 460
Gateway version than you purchased. Please contact Real Time
Automation, Inc. (RTA) at 262.439.4999 or www.rtaautomation.com
for more
information about 460 Gateway configurations.
460 Gateway User Manual Page 21