User manual
Default IP Address – 192.168.0.100
Note: Only one RS232, RS485, or CAN port setting can be active per unit. For example, a
unit cannot have two ports set for RS232 or two ports set for CAN.
To change port settings on the 460 EDX Gateway, use the following steps.
1. No cables should be connected to the Gateway unit. If this unit has been in use and you
are making a change, disconnect the power cable and any communications cables from
the Gateway unit.
2. Remove the two small Phillips-head screws from each long side (no connectors) of the
Gateway unit.
3. Remove the green T-Strip5 connector. Slide the cover off towards the ports. The jumpers
are just behind the ports.
4. Move the jumper shunts to reflect the desired settings. See Figure 2-1.
PIN
GND
GND
DB9
PORT 1
CAN
Pin 1
FD – Full Duplex
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
DB9
CAN Jumper
Configuration
JP6
JP7
JP8
JP11
JP12
JP13
JP14
JP15
JP16
JP5
JP9
JP10
JP4
Pin 1
FD – Full Duplex
- Required
- Optional
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
HSR
120T
PIN
JP20
JP21
JP18
JP22
JP28
JP2
JP27
JP19
JP17
JP3
PORT 0
T-Strip
CAN
T-Strip
CAN Jumper
Configuration
Pin 1
FD – Full Duplex
- Required
-Optional
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
JP6
JP7
JP8
JP11
JP12
JP13
JP14
JP15
JP16
JP5
JP9
JP10
JP4
DB9
PORT 1
RS232
DB9
RS232
Jumper
Configuration
Pin 1
FD – Full Duplex
- Required
-Optional
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
JP20
JP21
JP18
JP22
JP28
JP2
JP27
JP19
JP17
JP3
PORT 0
T-Strip
RS232
T-Strip RS232
Jumper
Configuration
Pin 1
FD – Full Duplex
- Required
- Optional
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
JP6
JP7
JP8
JP11
JP12
JP13
JP14
JP15
JP16
JP5
JP9
JP10
JP4
DB9
PORT 1
RS485
DB9
RS485
Jumper
Configuration
FD
FD
FD
PIN
Pin 1
FD – Full Duplex
- Required
- Optional
PIN – Power Input
HSR – High Slew Rate Control
120T – 120 Ohm Termination
JP20
JP21
JP18
JP22
JP28
JP2
JP27
JP19
JP17
JP3
PORT 0
T-Strip
RS485
T-Strip RS485
Jumper
Configuration
FD
FD
FD
FD
- Required
- Optional
Figure 2-1 Jumper settings
5. Replace the Gateway unit’s cover. Replace the four screws. Replace the green T-Strip5
connector.
Connecting a computer for software setup
Before performing the initial software setup, you must connect a computer with a web browser to
the 460 Gateway. Use the following steps to connect the computer and to access the embedded
web site where you make your software selections.
1. Connect one end of the Ethernet crossover cable to the 460 Gateway and the other end to
the RJ45 connector on your computer.
460 Gateway User Manual Page 5