Specification
SPLIT SYSTEM AIR CONDITIONER 4AC13
Page 9
Outdoor Model
Indoor
Model
Variable
Speed
Furnace
SEER EER
Rated
ARI
Capacity
1
BTUH
Rated
Sensible
Capacity
BTUH
CFM
Refrigerant
Connection
Refrigerant
Line Size
Indoor
Expansion
Device
Evaporator
Coil
or
Air Handler
3
Outdoor Indoor
Suction
Liquid
Piston
2
TXV
Suction
Liquid
Suction
Liquid
4AC13*30P
E(C,H,M,U)1P29B 80G1DF090BE16
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
0.063
A4TXV01
E(C,H,M,U)1P29B 80G1UH070BE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 80G1UH090BE16
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G1DF045BE12
13.5 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G1DF070BE16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G1UH045BE12
13.5 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G1UH070BE12
13.5 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G2DF045BV12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G2DF070BV16
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G2UH045BV12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 95G2UH070BV12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36A 80G1DF045AE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36A 80G1UH045AE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36A 80G2UH070AV12
13.5 11.5 28,000 21,000 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 80G1DF070BE12
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 80G1DF090BE16
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 80G1UH070BE12
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 80G1UH090BE16
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G1DF045BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G1DF070BE16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G1UH045BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G1UH070BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G2DF045BV12
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G2DF070BV16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G2UH045BV12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36B 95G2UH070BV12
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36C 95G1DF090CE16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36C 95G1UH090CE16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36C 95G2DF090CV20
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P36C 95G2DF110CV20
14.0 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES
* = B or L B = Wire Guard L = Louvered
Note:
1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240
2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required.
3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
4 For lines 25 ft or over, use 3/8"
5 For lines 25 ft or over, use 3/4"