Specification
SPLIT SYSTEM AIR CONDITIONER 4AC13
Page 8
Outdoor Model
Indoor
Model
Variable
Speed
Furnace
SEER EER
Rated
ARI
Capacity
1
BTUH
Rated
Sensible
Capacity
BTUH
CFM
Refrigerant
Connection
Refrigerant
Line Size
Indoor
Expansion
Device
Evaporator
Coil
or
Air Handler
3
Outdoor Indoor
Suction
Liquid
Piston
2
TXV
Suction
Liquid
Suction
Liquid
4AC13*24P
E(C,M,U)1P30B 80G1UH070BE12
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057
A4TXV01
E(C,M,U)1P30B 95G1DF045BE12
14.0 12.0 22,800 17,330 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G1UH045BE12
14.0 12.0 22,800 17,330 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G1UH070BE12
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G2DF045BV12
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G2DF070BV16
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G2UH045BV12
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
E(C,M,U)1P30B 95G2UH070BV12
14.0 12.0 23,000 17,480 800 3/4 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
4AC13*30P
BCS3M30C****P
BCE3M30C****P
13.0 11.0 28,000 21,000 1000 3/4 3/8 3/4 3/8 3/4 3/8
0.063
A4TXV01
BCS2M36V****P
14.0 12.0 28,000 21,000 1000 3/4 3/8 3/4 3/8 3/4 3/8
BCS3M30E****P
14.0 11.0 28,000 21,000 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23A 80G1DF045AE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23A 80G1UH045AE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23A 80G2UH070AV12
13.5 11.5 28,000 21,000 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 80G1DF070BE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 80G1DF090BE16
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 80G1UH070BE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 80G1UH090BE16
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G1DF045BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G1DF070BE16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G1UH045BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G1UH070BE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G2DF045BV12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G2DF070BV16
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G2UH045BV12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P23B 95G2UH070BV12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29A 80G1DF045AE12
13.5 11.5 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29A 80G1UH045AE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29A 80G2UH070AV12
13.5 11.5 28,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
E(C,H,M,U)1P29B 80G1DF070BE12
14.0 12.0 29,000 21,750 1000 3/4 3/8 3/4 3/8 3/4 3/8
COOLING PERFORMANCE WITH AIR HANDLERS AND FURNACES
* = B or L B = Wire Guard L = Louvered
Note:
1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240
2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required.
3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
4 For lines 25 ft or over, use 3/8"
5 For lines 25 ft or over, use 3/4"