Specification

SPLIT SYSTEM AIR CONDITIONER 4AC13
Page 3
Outdoor Model
Indoor
Model
SEER EER
Rated
AHRI
Capacity
1
Rated
Sensible
Capacity
CFM
Refrigerant
Connection
Refrigerant
Line Size
Indoor Metering
Device
Evaporator Coil3
or
Air Handler
3
Outdoor Indoor
Suction
Liquid
Piston
2
TXV
Suction
Liquid
Suction
Liquid
4AC13*18P
E(C,H,M,U)1P23(A,B)+TDR 13.00 11.00 17600 12800 650 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.053 A4TXV01
E(C,M,U)1P24(A,B)+TDR 13.00 11.00 17600 12800 650 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.053 A4TXV01
E(C,H,M,U)1P29A+TDR 13.00 11.00 17600 12800 650 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.053 A4TXV01
4AC13*24P
E(C,H,M,U)1P23(A,B)+TDR 13.00 11.00 22800 16800 800 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057 A4TXV01
E(C,M,U)1P24(A,B)+TDR 13.00 11.00 22800 16800 800 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057 A4TXV01
E(C,H,M,U)1P29A+TDR 13.00 11.00 22800 16800 800 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057 A4TXV01
E(C,M,U)1P30(A,B)+TDR 13.00 11.00 22800 16800 800 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057 A4TXV01
E(C,H,M,U)1P36(A,B,C)+TDR 13.00 11.00 22800 16800 800 5/8 3/8 3/4 3/8 5/8
5
3/8 or 1/4
4
0.057 A4TXV01
4AC13*30P
E(C,H,M,U)1P23(A,B)+TDR 13.00 11.00 28000 20400 1000 3/4 3/8 3/4 3/8 3/4 3/8 0.063 A4TXV01
E(C,M,U)1P24(A,B)+TDR 13.00 11.00 28000 20400 1000 3/4 3/8 3/4 3/8 3/4 3/8 0.063 A4TXV01
E(C,H,M,U)1P29A+TDR 13.00 11.00 28000 20400 1000 3/4 3/8 3/4 3/8 3/4 3/8 0.063 A4TXV01
E(C,M,U)1P30(A,B)+TDR 13.00 11.00 28000 20400 1000 3/4 3/8 3/4 3/8 3/4 3/8 0.063 A4TXV01
E(C,H,M,U)1P36(A,B,C)+TDR 13.00 11.00 28000 20400 1000 3/4 3/8 3/4 3/8 3/4 3/8 0.063 A4TXV01
4AC13*36P
E(C,H,M,U)1P36(B,C)+TDR 13.00 11.00 34000 25000 1200 3/4 3/8 7/8 3/8 3/4
6
3/8 0.072 A4TXV01
E(C,H,M,U)1P43(B,C)+TDR 13.00 11.00 34000 25000 1200 3/4 3/8 7/ 8 3/8 3/4
6
3/8 0.072 A4TXV01
E(C,H,M,U)1P50C+TDR 13.00 11.00 34000 25000 1200 3/4 3/8 7/ 8 3/8 3/4
6
3/8 0.072 A4TXV01
4AC13*42P
E(C,H,M,U)1P43C+TDR 13.00 11.00 40000 29200 1400 3/4 3/8 7/ 8 3/8 3/4
6
3/8 0.075 A4TXV01
E(C,H,U)1P49C+TDR 13.00 11.00 40000 29200 1400 3/4 3/8 7/ 8 3/8 3/4
6
3/8 0.075 A4TXV01
E(C,H,M,U)1P50C+TDR 13.00 11.00 40000 29200 1400 3/4 3/8 7/ 8 3/8 3 /4
6
3/8 0.075 A4TXV01
4AC13*48P
E(C,H,U)1P49C+TDR 13.00 11.00 47000 34300 1600 7/8 3/8 7/8 3/8 7/ 8 3/8 0.082 A4TXV02
E(C,H,U)1P62C+TDR 13.00 11.00 47000 34300 1600 7/ 8 3/8 7/ 8 3/8 7/ 8 3/8 0.082 A4TXV02
E(C,H,U)1P62D+TDR 13.00 11.00 47000 34300 1600 7/ 8 3/8 7/ 8 3/8 7/ 8 3/8 0.082 A4TXV02
4AC13*60P
E(C,H,U)1P49C+TDR 13.00 11.00 57000 41000 1800 7/8 3/8 7/ 8 3/8 7/8
7
3/8 0.090 A4TXV02
E(C,H,U)1P62C+TDR 13.00 11.00 57000 41000 1800 7/8 3/8 7/ 8 3/8 7/8
7
3/8 0.090 A4TXV02
E(C,H,U)1P62D+TDR 13.00 11.00 57000 41000 1800 7/ 8 3/8 7/ 8 3/8 7/8
7
3/8 0.090 A4TXV02
COOLING PERFORMANCE WITH EVAPORATOR COILS
1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240.
2 Required to achieve AHRI rating.
* = B or L B = Wire Guard L = Louvered
Note:
1 Certified in accordance with Unitary Air Conditioner Certification Program, which is based on AHRI Standard 210/240
2 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required.
3 A blower time delay relay is required to achieve AHRI rating. This feature is standard on all Allied Air Enterprises furnace and AH products.
4 For lines 25 ft or over, use 3/8"
5 For lines 25 ft or over, use 3/4"
6 For lines 25 ft or over, use 7/8"
7 For lines 25 ft or over, use 1-1/8"