User guide

INDUSTRIAL PIPE HIGH TEMPERATURE INSULATION
Acoustical Performance
ASTM E1222- Standard Test Method For Laboratory Measurement of the Insertion Loss of Pipe Lagging
Product Jacket
Frequency (Hz)
315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000
Insertion Loss (db)
12 x 1.5
Aluminum 3 -1 1 5 7 15 16 19 20 22 24 25 29
Stainless Steel 3 0 2 6 8 16 17 21 22 24 26 26 30
PVC 2 -4 -2 4 5 13 14 19 22 24 27 27 30
12 x 2
Aluminum 4 0 1 5 7 14 16 19 20 22 24 25 29
Stainless Steel 5 0 2 6 9 16 17 20 23 24 26 26 30
PVC 4 -1 0 4 6 12 14 18 21 24 026 26 30
12 x 2.5
Aluminum 3 0 1 6 7 14 16 20 21 23 25 26 29
Stainless Steel 3 0 1 7 9 15 18 21 23 24 26 26 30
PVC 1 -3 -2 4 2 11 14 19 21 24 26 25 29
12 x 3
Aluminum 3 -1 2 6 5 13 16 19 21 23 25 27 31
Stainless Steel 3 -1 2 6 6 14 17 20 23 24 26 27 31
PVC 2 0 1 3 2 11 15 19 23 25 28 28 31
12 x 4
Aluminum 3 1 4 7 10 16 18 22 24 26 28 28 31
Stainless Steel 3 1 5 8 11 18 19 23 25 26 28 28 31
PVC 3 1 3 5 5 15 18 22 25 27 29 28 31
ProRox PS 960
NA
is fire resistant and water repellent that saves energy,
while also providing optimal protection for personnel and equipment.
ProRox PS 960
NA
requires nothing more than a serrated knife for
precise cuts that can be made quickly and easily at the point of
installation, reducing waste and manpower hours.
ProRox
®
PS 960
NA
NEW
NAME
Formerly: ROXUL TECHTON
1200
®