Product Manual

Page 6 of 9
3
Press the MENU key. Keep it pressed until screen
displays an image similar to the image shown. The
first digit of the top display will flash to indicate the
meter is in correction factor modification mode.
4
Press the RESET key to choose the desired digit
from 0 to 9. Press the MENU key to start the next
digit. Each digit of the correction factor can be
changed individually.
5
Make sure the correction factor is correct, then press
the MENU key. Keep it pressed until reaching quit
calibration mode; the factor is automatically saved.
The meter returns to standby.
MODIFY THE CORRECTION FACTOR IN FIELD
Carefully follow the procedure indicated below.
1
Wait for the meter to go to standby.
2
Reset the resettable total as previously outlined in
Fig. 3.
3
Start dispensing into a measuring glass.
Stop dispensing when over 5 liters of volume is
reached, then check the actual dispensed value. The
volume that is displayed on the LCD is the Display
Value, not the Actual Value, which may be slightly
higher. For example, in the figure on the right, the
Display Value is 18.96 while the Actual Value is
20.75.
4
Press the MENU key. Keep it pressed until the
screen appears similar to the figure on the right, with
a digit flashing in the far left zone. Press the RESET
key to choose the correct digit from 0 to 9. Press the
MENU key to go the next digit and repeat the
process so that the Actual Value can be input.