Product Manual

Page 5 of 9
DISPLAY CURRENT CORRECTION FACTOR AND GENERAL TOTAL (See Fig. 4)
Press MENU and RESET together and hold for two seconds.
Value “1.4000” is the correction factor which can be reset;
1234567” is the general total which cannot be reset.
CHANGE MEASUREMENT UNIT (See Fig. 5)
Press MENU and RESET together and hold for five seconds or until Zone on the display shows the
current unit.
Press RESET to choose a different measurement unit.
When desired measurement unit is displayed, press MENU key and hold on for about 3 seconds to lock
in the new measurement unit.
CALIBRATION PROCEDURE
PROCEDURE FOR DIRECTLY ENTERING THE CORRECTION FACTOR
Carefully follow the procedure indicated below.
FORMULA
Example:
Actual value 20.75
Display value 18.96
Current correction factor 1.000
Proper correction factor 1.000×(20.75/18.96)=1.000×1.094=1.094
1
Wait for the meter to go to standby.
2
Reset the resettable total as outlined previously in
Fig. 3.
Fig. 5
Proper correction factor = current correction factor × (actual value/ display value)