Product Manual
Page 6 of 8
MODIFY THE CORRECTION FACTOR IN FIELD
Carefully follow the procedure indicated below.
1
Wait for the meter to go to standby.
2
Reset the resettable total as previously outlined in
Fig. 3.
3
Start dispensing into a measuring glass.
Stop dispensing when over 5 liters of volume is
reached, then check the actual dispensed value. The
volume that is displayed on the LCD is the Display
Value, not the Actual Value, which may be slightly
higher. For example, in the figure on the right, the
Display Value is 18.96 while the Actual Value is
20.75.
4
Press the MENU key. Keep it pressed until the
screen appears similar to the figure on the right, with
a digit flashing in the far left zone. Press the RESET
key to choose the correct digit from 0 to 9. Press the
MENU key to go the next digit and repeat the
process so that the Actual Value can be input.
5
Make sure the correction factor accurate, and then
press the MENU key. Keep it pressed until
calibration is finished and the factor is saved. The
meter will then return to standby.