Product Manual
Page 9 of 17
No.
Description
Qty.
No.
Description
Qty.
9
Discharge hose
1
28
O-ring
1
10
Elbow
1
29
Junction box cover
1
11
Bypass spring
1
30
Screw
6
12
Electric motor
1
31
Grounded screw
1
13
Pump chamber
1
32
Switch bracket
1
14
Bypass valve
1
33
Nozzle holder
1
15
O-ring
1
34
Nozzle
1
16
Filter screen
1
35
Screw
2
17
2” Bung adapter
1
36
Mechanical meter
1
18
Screw
2
37
Screw
2
19
Suction tube
1
Assembly Instructions
1. Tightly screw suction pipe into inlet coupling of pumping unit. Extend suction pipe into truck tank
or barrel to within 3” of tank bottom.
2. Screw inlet coupling of pump into 2” tank or barrel opening. Inlet coupling must be completely
and securely threaded into an undamaged tank or barrel bung.
3. During installation and maintenance, make sure that the electric supply lines are not live.
4. Always turn off the switch before supplying electrical power.
5. Check the correct rotation direction of the DC pump. If it is inverted, check the polarity of the
connection cable.
a) BLACK cable: positive pole (+)
b) WHITE cable: negative pole (-)
6. Systems should be designed to require a minimum amount of suction lift. Maximum “equivalent
feet of lift” is 8’ for diesel fuel.
7. Tank or barrel must be properly vented. A water separator should be used for pumping diesel
fuel.
8. DC Electrical:
8.1 Remove pump’s junction box cover and straighten the 2 wires to make the stripped wire
ends accessible outside of the junction box.
8.2 Screw furnished cable connector into 1/2” NPT conduit opening in pump junction box.
8.3 Strip 6 inches of the outer covering from one end of the furnished electrical cable being
careful not to damage the black and red wire insulation.
8.4 Loosen cable connector nut and pass the stripped end of the furnished cable through the
cable connector until 2 inches of the unstrapped cable is within the cable connector. Tighten
the cable connector nut.