8.5 Strip 1/2” of the installation from the ends of the red and black cable wires. Using the
furnished wire nuts, connect these wires to the pump wires matching the colors. Be sure no
bare wire is exposed.
8.6 Fold wires into junction box and replace cover making sure the gasket is in place. Make
sure all screws are seated so there is no space between the cover and the junction box.
Before Each Use
⚠WARNING
To prevent serious injury or property damage, read and understand owner’s manual before
operating.
Know and follow applicable national, state, and local safety codes pertaining to installing and
operating electrical equipment for use with flammable liquids.
Know and follow all safety precautions when handling petroleum fuels.
Ensure that all equipment operators have access to adequate instructions concerning safe
operating and maintenance procedures.
To ensure safe operation, all fuel transfer systems must be properly grounded. Proper grounding
means a continuous metal-to-metal contact from one component to the next, including tank, bung,
pump, meter, filter, hose, and nozzle. Care should be taken to ensure proper grounding during
initial installation and after any service or repair procedures.
To prevent physical injury, observe precautions against fire or explosion when dispensing fuel. Do
not operate the system in the presence of any source of ignition including running or hot engines,
lighted cigarettes, or gas or electric heaters.
Observe precautions against electrical shock when operating the system. Serious or fatal shock
can result from operating electrical equipment in damp or wet locations.
Make sure the power switch is in the off position before connecting power.
Wear the proper protective gear including ANSI Z87.1 compliant safety goggles while operating.
Observe precautions against electrical shock when servicing the pump. Always disconnect power
before repairing or servicing. Never apply electrical power to the system when any of the cover
plates are removed.
Disconnect circuit before removing cover and enclosure must be closed tightly when circuits are
live.
Operating Instructions
⚠WARNING
Know and follow applicable national, state, and local safety codes pertaining to installing and
operating electrical equipment for use with flammable liquids.
Know and follow all safety precautions when handling petroleum fuels.
Ensure that all equipment operators have access to adequate instructions concerning safe
operating and maintenance procedures.
To ensure safe operation, all fuel transfer systems must be properly grounded. Proper grounding
means a continuous metal-to-metal contact from one component to the next, including tank, bung,
pump, meter, filter, hose, and nozzle. Care should be taken to ensure proper grounding during
initial installation and after any service or repair procedures.