Examples:
6.4.5 Output Scale
The display range (Scale = ScaleHi - ScaleLo) of the Display-Value can be selected freely within the complete
display range (Display-Scale), but may not exceed the maximum display range of
-9,999…99,999.
The output range (Output-Range = RangeHi - RangeLo) of the output signal (Output-Value) can be selected
freely within the complete output range (Voltage- / Current-Range), but may not exceed the maximum output
range, cf. chapter 3.5 (0…1 V / 0…5 V / 0…10 V / 0…24 mA / 4…24 mA). Fixed values (Fix-Value) are treated
in the same way as Display-Values.
Figure 17: Graphic representation of scaling the analog output