Instruction Manual
Dokument 
UMA 146 
Rev 
1 
Page 
3 (7)
Terminal 
Default 
Output 
Default Output 
Range 
Outputs of this 
sensor 
Output Range of 
this sensor 
Out(1) 
0-10VDC 
0-2000 ppm CO
2
0-10VDC 
0-4 % CO
2
Out(2) 
0-10VDC 
0-50 
o
C  
Relay 
Closed 
Open 
> 1000 ppm CO
2 
< 900 ppm CO
2 
> 2,0 % CO
2 
< 1,9 % CO
2 
Table I. Default output configurations for CF8-W-Disp-GH  
Formulas for calculation of output values 
Configuration 
Output Range 
Formula for calculation 
0-10 VDC 
0-2000 ppm CO
2 
0-50 
o
C 
CO
2
 value = Volt/10*2000 
Temperature value in
 o
C = Volt/10*50 
2-10 VDC 
0-2000 ppm CO
2 
0-50 
o
C 
CO
2
 value = (Volt –2)/8*2000  
Temperature value in
 o
C = (Volt –2)/8*50 
4-20 mA 
0-2000 ppm CO
2 
0-50 
o
C 
CO
2
 value = (mA-4)*2000/16  
Temperature value in
 o
C = (mA-4)*50/16 
a-b 
c–d 
Value = (reading-a)/(b-a)*(d-c)+c 
a = lowest value of the configuration 
b = highest value of the configuration 
c = lowest value of the range 
d = highest value of the range 
Table II. Calculation of CO
2
 value and temperature value for CF8-W-Disp-GH 
The red LED is lit when the relay output is closed. 
Output Configurations 
The sensors/controllers are supplied from the factory (unless otherwise ordered) with 
0...10VDC linear outputs for Out(1)  and Out(2)  (see Table I). If other options are 
needed for the application, the output jumpers have to be configured before the unit 
is powered up. Each jumper selection is independent from the others, except for the 
“Start point selection” jumper, which affects both, Out(1) and Out(2), linear outputs.  