UMA 145 
Rev 
3 
Page 
3 (8)
Terminal 
Default 
Output 
Default Output 
Range 
Outputs of this 
sensor 
Output Range of this 
sensor 
OUT1 
0-20 mA 
0-4 % CO
2
OUT2 
4-20 mA 
0-4 % CO
2
Relay 1 
Closed 
Open 
> 1,5 % CO
2 
< 1,4 % CO
2 
Relay 2 
Closed 
Open 
> 3,0 % CO
2 
< 2,9 % CO
2 
Table I. Default output configurations for CF8-W-Disp-AL 
Formulas for calculation of output values 
Configuration 
Output Range 
Formula for calculation 
0-10 VDC 
0-4 % CO
2 
CO
2
 value = Volt/10*4 
2-10 VDC 
0-4 % CO
2 
CO
2
 value = (Volt –2)/8*4 
4-20 mA 
0-4 % CO
2 
CO
2
 value = (mA-4)*4/16  
a-b 
c–d 
Value = (reading-a)/(b-a)*(d-c)+c 
a = lowest value of the configuration 
b = highest value of the configuration 
c = lowest value of the range 
d = highest value of the range 
Table II. Calculation of CO
2
 value for CF8-W-Disp-AL 
Output Configurations 
If other options are needed for the application, the output jumpers have to be 
configured before the unit is powered up. Each jumper selection is independent from 
the others, except for the “Start point selection” jumper, which affects both, Out(1) & 
Out(2), linear outputs. Alternative measuring ranges of the outputs can be selected 
with the software UIP (version 4.3 or later). 