User Guide

16 20-5110 Issue B
Alarm Setpoint 1 Default: 100.0
Defines the alarm setpoint for Alarm 1 in display units.
As Alarm Setpoint 1 if Alarms 2 and 3 are fitted.
Relay 1 Default: True
Defines the operation of Relay 1, which can be in either the
energised alarm state (truE) or the de-energised alarm state (FLSE).
As Relay 1 if Alarms 2 and 3 are fitted.
A100 Default: 100.0
Defines the display value which corresponds to 20mA from the
optional analogue retransmission.
A0 Default: 0.0
Defines the display value which corresponds to 4mA from the
optional analogue retransmission.
Key 1
On units fitted with the front panel buttons, the following
functions may be assigned to either or both function keys: zero, tare,
display high (maximum) or low (minimum) value since last reset or reset
of the high and low values to the current measured value.
Key 2
As for Key 1.
Default Default: Off
Allows the instrument to be returned to its factory supplied
setup.
dFLt
KEY2
KEY1
A0
A100
rEL2 rEL3
rEL1
SP-2 SP-3
SP-1
Sentry Digital Panel Indicator
Setup Guide