AC-Q4x Series Installation and Programming Manual 39
auxiliary relay matches the condition of the magnetic contact
switch; if the door opens, the auxiliary relay opens; if the door
closes, the auxiliary relay closes. When a valid code is entered, a
countdown for maximum Shunt time, as defined by the auxiliary
setting, begins; if the door is not closed before the maximum Shunt
time, the alarm is triggered.
4.9.7 Auxiliary Mode 6
Auxiliary input function: Door Monitor
Auxiliary output activated by: Forced entry
For example, in Auxiliary Mode 6, the controller can trigger the
auxiliary relay if the door has been forced. If the Siren Settings is
enabled, the siren is activated.
In this mode, the auxiliary input functions as a door monitor switch
and is wired to the magnetic contact switch on the door. The
auxiliary relay is to be wired to the alarm system. If the door is
forced open, the controller waits for the period of the Forced Door
Delay time to elapse and then it activates the auxiliary relay. The
auxiliary setting sets the forced door delay period.
4.9.8 Auxiliary Mode 7
Auxiliary input function: Door Monitor
Auxiliary output activated by: Door Ajar (door held open)
For example, in Auxiliary Mode 7, the controller can trigger the
auxiliary relay, if it detects that the door has been held open (ajar)
too long. In this mode the auxiliary input functions as a door
monitor switch and is wired to the magnetic contact switch on the
door. The auxiliary relay is to be wired to the alarm system. If the
door is opened, the controller waits for the Door Ajar Delay time to
elapse and if the door does not close prior to the end of this period,
the controller activates the auxiliary relay. The auxiliary setting
defines the Door Ajar time.