Instruction manual
Auxiliary
Mode
Auxiliary Mode Quick Reference Table
0 REX-2 Valid Code or REX-2 N.O. 01 to 99 Aux. Relay Release Time
00 Aux. Relay Toggles
1 Normal / Secure Valid Code N.O. 01 to 99 Aux. Relay Release Time
00 Aux. Relay Toggles
2 Normal / Secure Star Button N.O. 01 to 99 Aux. Relay Release Time
00 Aux. Relay Toggles
3 Normal / Secure Tamper Event N.C. 01 to 99 Aux. Relay Release Time
00 Aux. Relay activated by Tamper
4 Normal / Secure Direct Shunt N.O. 00 to 99 Shunt Time
5 Door Monitor Shunt N.C. 00 to 99 Maximum Shunt Time
6 Door Monitor Forced Door N.C. 00 to 99 Forced Delay
7 Door Monitor Door Ajar N.C. 00 to 99 Ajar Delay
8 LED Ctrl - Red Valid Code N.O. 01 to 99 Aux. Relay Release Time
00 Aux. Relay Toggles
9 LED Ctrl - Green Valid Code N.O. 01 to 99 Aux. Relay Release Time
00 Aux. Relay Toggles
Auxiliary Input
Function
Auxiliary Output
Activated On
Auxiliary Settings Aux.
Relay
(All times and delays are in seconds)
Page 28
07/04
Setting the Auxiliary Mode
The default auxiliary setting is 2004.
1) Enter Programming Mode
2) Press "6" to enter Menu 6
l
The Mode LED will flash green
3) Construct the 4-digit code
using the instructions below:
Auxiliary Mode
Auxiliary Setting
Auxiliary Mode
In addition to the Lock Strike Relay and Lock Strike REX, the
AC-Q41H features an Auxiliary Output Relay and an Auxiliary
Input. The Auxiliary Mode defines the function of the Auxiliary
Input and Output.
The Auxiliary Mode also determines if the Auxiliary Output Relay
is set for Fail Safe or Fail Secure Operation.
Auxiliary Settings
Each of the Auxiliary Modes has a two digit setting that affects
how the Auxiliary Mode functions.
4) System returns to Normal Mode
l
You will hear three beeps
l
The Door LED will turn off.
l
The Mode LED will turn green
The Auxiliary Mode Quick Reference Table can be found on the
next page. For a more detailed explanation on each auxiliary mode
refer to the "Auxiliary Mode Reference Guide" on page 30.
AC-Q41H
Mode Door
GREEN
Mode Door
GREENGREEN
2
?
?
?
Mode Door
GREEN