User guide
Table Of Contents
- 1. Introduction
- 2. Specifications and Requirements
- 3. Installation
- 4. System Overview
- 5. How to Set Up a Site
- 5.1 Adding Time Zones
- 5.2 Adding Holidays
- 5.3 Adding a Network
- 5.4 Adding Access Control Panels
- 5.5 Configuring the Doors
- 5.6 Configuring the Readers
- 5.7 Configuring the Inputs
- 5.8 Adding a Camera
- 5.9 Adding Panel Links
- 5.10 Creating Groups
- 5.11 Adding Users and Cards
- 5.12 Adding Departments, Users, and Visitors
- 5.13 Adding Access Areas
- 5.14 Adding Global Antipassback Rules
- 5.15 Car Parking
- 5.16 Adding Operators
- 5.17 Creating Elevator Control
- 5.18 Creating Status Maps
- 6. ViTrax™ Video Integration
- 7. Manual Operation
- 8. AxTraxNG™ Reports
- 9. Administrator Operations
- A. Firewall Configuration
- B. SQL Service Settings
- C. Network Configuration
- D. Restoring Factory Default Settings
- E. Configuring User Counters
- F. Cross Platform Camera Setup
- G. Enrolling Cards using MD-08 Desktop Reader
- H. SQL Server Installation Troubleshoot
- I. AxTrax.NET Watchdog
- J. Adding Custom Wiegand Formats

How to Set Up a Site
AxTraxNG™ Software Installation and User Manual 59
5.9.1 Creating a Fire Alarm Input
You can configure the panel properties to generate a fire alarm warning.
To create a fire alarm input:
1. In the Tree View, click AC Networks.
2. Select a network and expand a panel in the Tree View.
3. Select AC Links.
4. On the
Network
toolbar, click the icon.
The
Add Link
window opens.
5. Configure the link as follows:
a. In Source Type, select Input.
b. In Destination Type, select Output Group.
c. In Operation, select Timer.
d. Select the Generate Alarm checkbox.
6. Click Alarm Handler.
The
Alarm handler
window opens.