AC-215 Single and Double Door Access Control Unit Hardware Installation Guide September 2003
Copyright and Version Number Information in this document, including URL and other Internet Web site references, is subject to change without notice. Unless otherwise noted, the example companies, organizations, products, people and events depicted herein are fictitious and no association with any real company, organization, product, person or event is intended or should be inferred. © Copyright 2003 Rosslare. All rights reserved.
Limitation of Liability THE WARRANTIES SET FORTH IN THIS AGREEMENT REPLACE ALL OTHER WARRANTIES. ROSSLARE EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES, INCLUDING BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OF THIRD PARTY RIGHTS WITH RESPECT TO THE DOCUMENTATION, SOFTWARE, AND HARDWARE. NO ROSSLARE DEALER, AGENT, OR EMPLOYEE IS AUTHORISED TO MAKE ANY MODIFICATION, EXTENSION, OR ADDITION TO THIS WARRANTY.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Table of Contents Introduction to the AC-215 ACU ...................................................................................... 1 Main Features..................................................................................................................................................2 Software .............................................................................................................................
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide About this manual This manual is intended for anybody installing and or commissioning the AC-215 access control system. ! We recommend that this manual be read in full before the Veritrax software and AC-215 Access Control System installed.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Introduction to AC-215 ACU The AC-215, access control system, and the Veritrax PC software are combination that gives full control over the entrances of your premises. Veritrax software supports control for both single and double door entrances where up to 32 AC-215 Access Control Units (ACU) can be monitored. AC-215 employs the latest technology to meet the requirements of the market.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Main Features AC-215 ! Two IN/OUT readers ! Four Inputs ! Four Outputs ! Optional secure mode that requires card and PIN entry ! Antipassback real and time with forgive feature ! Up to 4 different site codes ! Automatic operation by time zone for every output ! Optional first person delay before automatic door unlocking ! Optional expanded lock operation time ! Activated auxiliary output by reader transactions
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide AC-215 Single and Double Door Access The access to an entrance is first set as either single or double door in the Veritrax software, this definition is then downloaded to the panel.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Software Veritrax software is user friendly and intuitive. Its graphic interface is used to define settings, which are downloaded to the ACU and event logs which are uploaded to the PC to generate reports. A single server, which communicates to and from the ACU, can serve unlimited network clients. The system’s database is saved in the server. The database can be set to backup and can input/export previous configurations.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Technical Specifications This chapter discusses the technical specification required for the system. Electrical Specifications Main Unit Operating Voltage: 12V DC 0.5A From PS-14 Maximum Input Current: (Not including attached devices) Standby: 125mA Maximum: 325mA Outputs Relay Outputs: 5A Relay N.O. and N.C. options Inputs General Inputs: High impedance active low inputs.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Environmental Specifications Operating Temperature: -25°F to 145°F (-31°C to 63°C) Operating Humidity: 0 to 95% (Non-condensing) Mechanical Specifications Enclosure's Dimensions: 10.4” (264mm) L x 13.2” (334mm) W x 3.4” (84.5mm) D Weight: 8.31 lbs (3.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Inputs and Outputs This chapter discusses the AC-215 ACU input and output requirements. Inputs Release to Exit Button (REX) REX enables quick exit from a premises. The following should be defined: Single door controller: Door 1 - IN1 Double door controller: Door 1 - IN 1 Door 2 - IN 2 Usually the REX input is connected to a push button that is located inside the premises.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Tamper The Tamper input connects to a tamper micro switch assembled within the ACU panel. The following should be defined: Single door controller: Door 1 – IN2 Tamper input is activated when the panel is opened through vandalism. The system has two additional tamper inputs on the reader terminals. General The General input connect to any general-purpose dry contact input.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Door Alarm This output is activated when either an alarm occurs in the system, or automatically by a time zone.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Card Readers Two card readers can be connected to the ACU. The following should be defined: Single door controller: Door 1 – Reader 1 IN/OUT/auxiliary Reader 2 IN/OUT/auxiliary Double door controller: Door 1 – Reader 1 IN/OUT Door 2 – Reader 2 IN/OUT The readers can be assigned to a single or double door controller’s door as an IN or OUT reader and can activate the auxiliary output in a single door configuration.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Dipswitch Settings Configuration The ACU Dipswitch controls a number of operating parameters including the device address and baud rates for serial communication. 1 2 3 4 5 6 7 8 ! Power down the ACU before making changes in the dipswitch settings. Restart the ACU after modifications are made. The new settings are automatically defined after power up.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide The following lists switch 1 and 2 status and baud rate: Switch 1 Switch 2 Baud Rate Off Off On On Off On Off On 9600 19200 38400 56000 ! The ACU baud rate must be identical to the host PC’s serial port baud rate ACU Type The ACU type is defined using the third dipswitch. Both the single and double can be set.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Double Door Controller This access type has two readers, IN and OUT, as follows: Outputs: Door 1 lock strike Door 1 alarm output Door 2 lock strike Door 2 alarm output Inputs: Release to exit door1 Door 1 monitor input Release to exit door 2 Door 2 monitor input ACU Addressing The dipswitch is used to select the binary coded ACU address. 1 2 3 4 5 6 7 8 ! The ACU address is defined in the Veritrax software.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide The following table gives all the 32 dipswitch settings available.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Communications Communication lines are used to upload and download information between the ACU and the Veritrax software. Communication between the ACU and PC is displayed by the system’s two LEDs. ! The RX LED flashes when the controller receives data ! The TX LED flashes when the controller transmits data ! The ACU address is defined in the Veritrax software.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide RS485 Connection to the PC Up to 32 ACU's can be linked together and connected to a single communication port on the PC. The RS485 interface must be used when multiple controllers are connected. The serial port used to control the ACU is assigned in the Veritrax software Network Properties dialog box. ACU supports the two-wire RS485 interface.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Communication through the Local Area Network (LAN) The TCP/IP connection, used to control the ACU, is assigned in the Veritrax software’s Network Properties dialog box. The PC running the VeriTrax software can communicate with the ACU through the LAN card inside the PC. The ACU connects to the LAN using Rosslare MD-N32 TCP/IP to RS232 gateway converter.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Wiring Inputs The following diagrams illustrate wiring for four AC215 inputs. For further details refer to the Inputs and Outputs chapter page 7..
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Outputs The following diagrams illustrate wiring for two main types of 12VDC electric release mechanisms. Other electrical devices can be switched using the voltage free relay contacts. . Door Lock – Fail Closed IN 1A 0UT 1A (+) 12-24AC/DC (-) 12-24 AC/DC Alarm READER 1 IN 1 OUT 1 Lock Diode IN4004 (+) 12VDC (-) Door Lock – Fail Open READER 1 IN 1 (-) 12VDC (+) 12VDC 1.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Power Supply The following diagram illustrates wiring between the PS-14 power supply and the AC215. It is recommended to add a 12VDC lead acid backup battery to backup power if the main fails. If the main output is 12VDC wire it to the (PS-14), otherwise support your power supply according to output requirements. For further information refer to the Output requirements page 7..
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Key +V Red (-) Black D0 Green D1 White G.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Accessories Proximity Readers AY-X09 Series PIN Readers " AY-C09 / AY-D09 ! For indoor use ! Slim stylish design (Mullion) ! Includes LED indicator ! Audible buzzer indicator ! Built in tamper (w/ Rosslare controllers) ! Includes bell button (w/ Rosslare controllers) AY-X11 Series Prox Readers w/ Bell " AY-C11 / AY-D11 ! Reading distance: 8 to 10cm ! RF modulation: ASK at 125 kHz ! For indoor use ! Slim sty
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide AY-X12 Series Prox Readers " AY-C11 / AY-D11 ! Reading distance: 8 to 10cm ! RF modulation: ASK at 125 kHz ! For indoor use ! Slim stylish design (USA gang box) ! Bi-color light indicator ! Audible buzzer indicator (w/ Rosslare controllers) ! Built in tamper (w/ Rosslare controllers) AY-X12 Series Prox Readers " AY-H12 / AY-J12 / AY-K12 / AY-L12 / AY-M12 ! Reading distance: 7 to 12cm ! RF modulation: ASK at
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide AY-X19 Series Pin & Prox Readers " AY-C19 / AY-D19 ! Reading distance: 8 to 10cm ! RF modulation: ASK at 125 kHz ! For indoor use ! Slim stylish design (USA gang box) ! Bi-color light indicator ! Audible buzzer indicator ! Built in tamper (w/ Rosslare controllers) ! Includes bell button (w/ Rosslare controllers) AY-L23 RF Reader " AY-L23 ! Read range: 70 meters (200 feet) ! For outdoor use (waterproof) !
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Appendix Connecting Between MD-N32 & AC-215 Hardware Requirements ! Standard LAN cable - RJ45 plugs in both sides. ! Rosslare's MD-14. ! Rosslare's MD-N32 (only one unit required). ! Rosslare's AC-215. Instructions Manual Notes 1. The next connection instructions relates to an example of connecting one unit of Rosslare's AC-215 to one unit of MD-N32. The AC-215 is managed by a PC, running Rosslare's VeriTrax PC S/W.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Running the MD-32 configuration Software 1) Run the PC software: "IIM_CfgTool". 2) Click on the tab: "Search". Make sure that you see the right MD-N32's MAC Address on the “Board List” area . 3) Select the MAC Address of the unit that connects to the AC-215. 4) Make sure to empty the "Debug mode" tab (must to do when working with AC-215).
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Running and configuring VeriTrax On the PC (That connects to the same LAN as the MD-N32) run the VeriTrax SW. Configure a new Network .The network type should be TCP/IP (as shown on the example below). Type the same IP Address and port number that you configured on the MD-N32. Press OK . Configure a new Panel and Press OK .
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Power Supply Specifications ACU uses the PS-14 power supply. Transformer Input voltage: 230V AC Output voltage: 16V AC Output current: Maximum: 2.5A (40VA) PS-14 Power Supply Input voltage/current: 16V AC/2.5A From transformer Output voltage1: Backup battery charger Output voltage #2: 13.8V (12VDC/300mA) 12VDC/0.5A ACU Output voltage #3: 12VDC/1.
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide PS-14 Power LEDs Power in (AC) Green LED1 Main power Power out (DC) Red LED2 Low voltage Charger (BAT) Red LED3 Back up battery low voltage 29
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide Index A AC215 Single Door Controller, 13 AC315 Dual Door Controller, 14 Accessories AY-L23 Readers, 26 AY-X09 Series PIN Readers, 24 AY-X11 Series Prox Readers w/ Bell, 24 AY-X12 Series Prox Readers, 24, 25 AY-X19 Series PIN and Prox Readers, 26 ACP Addressing, 14 ACP Baud Rate, 12 ACP Type, 13 Auxiliary, 10 Inputs and Outputs, 8 Auxiliary, 10 Door Alarm, 10 Door Lock, 9 General, 9, 10 Tamper, 9 K Keypads, 11 M Main Features ACP
AC-215 Single and Double Door Access Control Unit Hardware Installation Guide T Tamper, 9 Technical Specifications, 27 Electrical Specifications, 5 Indicators and Annunciators, 5 Inputs, 5 Outputs, 5 Power Supply, 27 Power Supply Indication, 27 Power-14 LEDS, 28 Transformer, 27 Technical Support, 31 Transformer, 27 V Veritrax Main Features, 2 Software, 4 Veritrax - Introduction, 1 W Wiring, 20, 21, 22 Inputs, 20 Outputs, 21 Power Supply, 22 Reader, 22 31
Technical Support International Web Site http://www.rosslare.com.hk Asia, Australia and South America Rosslare Enterprises Ltd 905-912 Wing Fat Industrial Bldg 12 Wang Tai Road, Kowloon Bay Hong Kong Tel: (852) 2795 5630 Fax: (852) 2795 1508 Email: info@rosslare.com.hk United States and Canada Rosslare NAPDC 200 East Howard Street, Suite 238 Des Plaines IL 60018 Tel: (847) 827 6330 Fax: (847) 827 6433 Email: support@rosslare.