Fire Verify
Double checks the state of the fire
detectors.
When there is a fire sensor alarm signal,
a siren is heard immediately. A 60-
second retard-reset period starts during
which every additional fire alarm signal is
ignored. After this period, an additional
timeout of 60 seconds starts, which is
the confirmation period, during which a
fire sensor alarm signal causes an event
transmission to the monitoring station.
When the confirmation period expires,
the fire zone is automatically restored
and ready for a new fire alarm session.
Disabled
Recent Close Time
A Recent Closing transmission is sent if
an alarm occurs within the
programmable time after the Exit Time
passes.
2 minutes
Swinger Time
Duration for automatic resetting of
detectors after being ignored by swinger
trips
8 hours
Unvacated Premises
Triggers Arm Home (Stay) mode
automatically if the system was armed in
Arm Away mode but there was no
exiting from the premises during exit
delay
Enabled
Squawk Buzzer
Determines whether the buzzer sounds
when arming or disarming the panel for
remote operation.
Enabled
Siren
Determines whether the siren sounds
when arming or disarming the panel for
remote operation.
Enabled
To set the Abort Annunciation:
1. Using Menu, select either Enabled or Disabled.
2. Press Enter to confirm.
To set the Cancel Annunciation:
1. Using Menu, select either Enabled or Disabled.
2. Press Enter to confirm.
To set the Fire Verification:
1. Using Menu, select either Enabled or Disabled.
2. Press Enter to confirm.