User's Manual
Table Of Contents
- 1. Introduction
- 2. Technical Specifications
- 3. Mounting
- 4. Wiring Instructions
- 5. OSDP Operation
- 6. Reader Functionality
- 6.1 Transmit Mode
- 6.2 Programming as a Reader
- 6.3 Setting the Backlight
- 6.4 Return to Factory Default Settings
- 6.5 Replacing a Lost Programming Code
- 7. Controller Functionality
- 7.1 Normal, Secure, and Master Users
- 7.2 Modes of Operation
- 7.3 Auxiliary Input and Output
- 7.4 Door Alarms
- 7.5 Internal Case and Back Tamper
- 7.6 Lockout Feature (Keypad/Card Tamper)
- 7.7 REX Function
- 7.8 Secured Intelligent Power Supply
- 7.9 Programming as a Controller
- 7.9.1 Entering Programming Mode
- 7.9.2 Exiting Programming Mode
- 7.9.3 Changing Lock Strike Code
- 7.9.4 Changing Auxiliary Code
- 7.9.5 Changing the Programming Code
- 7.9.6 Changing the Normal/Secure Code
- 7.9.7 Changing the Normal/Bypass Code and Door Chime Settings
- 7.9.8 Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time
- 7.9.9 Defining the Auxiliary Input and Output
- 7.9.10 Auxiliary Mode Reference Guide
- 7.9.11 Setting the Lockout Feature
- 7.9.12 Setting the Backlight Behavior
- 7.9.13 Setting the Bell Button (*) Behavior
- 7.9.14 Enrolling Primary and Secondary Codes
- 7.9.15 Deleting Primary and Secondary Codes
- 7.9.16 Relay Codes Assignment
- 7.9.17 Relay Code Assignment using Standard Method
- 7.9.18 Relay Code Assignment using Search Method
- 7.9.19 PIN Code Length/Factory Default Settings
- 7.9.20 Replacing a Lost Programming Code
- 7.9.21 Exiting Secure Mode if Normal/Secure Code was Lost
- A. Declaration of Conformity
- B. Limited Warranty
Controller Functionality
52 AYC-x6355 (Rev. A) Installation and User Manual
7.9.10.5 Auxiliary Mode 6
Auxiliary input function: Door Monitor
Auxiliary output activated by: Forced entry
For example, in Auxiliary Mode 6, the controller can trigger the
auxiliary relay if the door has been forced. If the siren settings are
enabled, the siren is activated.
In this mode, the auxiliary input functions as a door monitor switch
and is wired to the magnetic contact switch on the door. The auxiliary
relay is to be wired to the alarm system. If the door is forced open,
the controller waits for the period of the forced door delay time to
elapse and then it activates the auxiliary relay. The auxiliary setting
sets the forced door delay period.
7.9.10.6 Auxiliary Mode 7
Auxiliary input function: Door Monitor
Auxiliary output activated by: Door Ajar (door held open)
For example, in Auxiliary Mode 7, the controller can trigger the
auxiliary relay if it detects that the door has been held open (ajar) too
long. In this mode, the auxiliary input functions as a door monitor
switch and is wired to the magnetic contact switch on the door. The
auxiliary relay is to be wired to the alarm system. If the door is
opened, the controller waits for the Door Ajar Delay time to elapse
and if the door does not close prior to the end of this period, the
controller activates the auxiliary relay. The auxiliary setting defines the
Door Ajar Delay time.