Manual

36 © 2012, ROSS CONTROLS
®
. All Rights Reserved.
TURCK Modular Industrial I/O System BL 67
Deluxe 4 Discrete Input
4 Discrete Output Module
Electrical: Operating Current: <30 mA from V
MB
<100 mA from V
O
Output Current: <0.5 A per output from V
O
Power Distribution: Inputs: V
O
Logic: V
MB
and V
O
Material: Connectors: Nickel-plated brass
Housing: PC-VO (Lexan)
Diagnostics (Logical): Diagnostic information available through the fieldbus gateway
Diagnostics (Physical):
LED to indicate module bus communication status as well
as I/O diagnostics
• LEDs for each I/O point to indicate on/off status
BL67-4DI4DO-PD
D
BAC
3.583
(91.0)
1.654 (42.0)
1.260 (32.0)
7.677
(195.0)
Diagnostic
LEDs
I/O LEDs
I/O
Connectors
Diagnostic
LEDs
I/O
LEDs
I/O
Connectors
Inputs Outputs Data
Part Number
Drawing
Input Count
Connectors
Pinout
Inputs per
Connector
Sensor
Style
V
I
+ Avail.
Current
Group
Diagnostics
Individual
Wire-Break
Detection
Output Count
Connectors
Pinout
Outputs per
Connector
Current
Individual
Diagnostics
Wire-Break
Detection
I/O Map
BL67-4DI4DO-PDwith BL67-B-4M12-P* A 4 0-1 2S 2 PNP X 4 2-3 2G 2 0.5 A X 1
BL67-4DI4DO-PD with BL67-B-4M12* B 4 0-3 C 1 PNP X 4 0-3 C 1 0.5 A X 1
BL67-4DI4DO-PD with BL67-B-8M8* C 4 0-3 PI 1 PNP X 4 4-7 PO 1 0.5 A X 1
BL67-4DI4DO-PD with BL67-B-1M23* D 4 0 M23 4 PNP 80 mA each 4 0 M23 4 0.5 A 1
BL67-4DI4DO-PD with BL67-B-1M23* D 4 0 M23 4 PNP 4 a total 4 0 M23 4 0.5 A
M23
1 = Input
0
2 = Input
1
3 = Input
2
4 = Input
3
5 = Output
0
6 = Output
1
7 = Output
2
8 = Output
3
9 = V
I
+
10 = V
I+
11 = V
I+
12 = V-
Shown with
BL67-B-4M12 base
Input/Output Connectors
PI
Mating cordset: PSG 3M-*
2S
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter: VBRS 4.4-2RK 4T-*/*
2G
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter: VBRS 4.4-2RK 4T-*/*
C
Mating cordset:
RK 4.4T-*-RS 4.4T
Splitter:
VB2-RS 4.4T-1/2RK 4.4T-*/*/S651
I/O Data Map 1
Note: I/O faults can be reported in the I/O map. Consult the product user
manual for details.
In
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n-1 (Data for modules to the left)
n Data for next discrete modules I-3 I-2 I-1 I-0
n+1 (Data for modules to the right)
Out
n-1 (Data for modules to the left)
n Data for next discrete modules 0-3 0-2 0-1 0-0
n+1 (Data for modules to the right)
Modular I/O Fieldbus Independent Configuration • IP 67 Protection • Various I/O Styles