Manual

31www.rosscontrols.com
TURCK Modular Industrial I/O System BL 67
8 Discrete Output Modules
Electrical: Operating Current: <30 mA from V
MB
<100 mA from V
O
Output Current: <0.5 A per output from V
O
Power Distribution: Inputs: V
O
Logic: V
MB
and V
O
Material: Connectors: Nickel-plated brass
Housing: PC-VO (Lexan)
Diagnostics (Logical): Diagnostic information available through the fieldbus gateway
Diagnostics (Physical): LED to indicate module bus communication status as well as I/O diagnostics
 LEDs for each I/O point to indicate on/off status
BL67-8DO-0.5A-P
DABC
3.583
(91.0)
1.654 (42.0)
Diagnostic
LEDs
I/O LEDs
I/O
Connector
1.260 (32.0)
7.677
(195.0)
Outputs Data
Part Number Drawing
Output
Count
Connectors Pinout
Outputs per
Connector
Current Style
Individual
Diagnostics
I/O
Map
BL67-8DO-0.5A-P with BL67-B-4M12* A 8 0-3 2G 2 0.5 A Source 1
BL67-8DO-0.5A-P with BL67-B-4M12-P* B 8 0-3 2G 2 0.5 A Source 1
BL67-8DO-0.5A-P with BL67-B-8M8* C 8 0-7 PO 1 0.5 A Source 1
BL67-8DO-0.5A-P with BL67-B-1M23 D 8 0 M23-4O 4 0.5 A Source 1
2G
Mating cordset: RK 4.4T-*-RS 4.4T
Splitter: VBRS 4.4-2RK 4T-*/*
PO
Mating cordset: PSG 3M-*
M23-8O
1 = Output
0
2 = Output
1
3 = Output
2
4 = Output
3
5 = Output
4
6 = Output
5
7 = Output
6
8 = Output
7
9 = V
I
+
10 = V
I
+
11 = V
I
+
12 = V-
1
4
3
5
2
6
7
8
9
10
11
12
Modular I/O Fieldbus Independent Configuration • IP 67 Protection • Various I/O Styles
Outputs Connectors
I/O Data Map 1
Shown with
BL67-B-8MB base
Application:
TURCK splitter box: 8MB12Z-4PZ-CS12
Cable: CSWM CKWM 12-10-*/S101/BL67
Out
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
n-1 (Data for modules to the left)
n 0-7 0-6 0-5 0-4 0-3 0-2 0-1 0-0