Reference Manual
39
Reference Manual
00809-0100-4045, Rev AB
Troubleshooting
March 2016
Troubleshooting
Failure
Configuration
Alert
The device has detected a
configuration error.
1.Click on details for more information.
2. Correct the parameter that has a configuration
error.
3. Reset the device.
4. If the condition persists, replace the device.
Over-pressure
Seen
The pressure has gone
beyond the maximum
operating limits of the
device, which may have
caused permanent
damage to the sensor.
1. Check the pressure applied to ensure it is within the
sensor limits.
2. Check the device pressure connection to make sure
it is not plugged or that the isolating diaphragms
are not damaged.
3. Acknowledge the over pressure condition to clear
the latched indication, and verify the integrity of
the sensor.
4. If the condition persists, replace the device.
Critical Power
Failure
The supply voltage is too
low for the device to
broadcast updates.
1. Replace the battery.
Electronics
Failure
An electronics error that
could impact the device
measurement reading has
occurred.
1.Restore device to default settings.
2. Perform a Device Reset.
3. If the condition persists, replace the device.
Dial Failure
The device is no longer
able to validate the
position of the dial.
1. Reset the device.
2. If condition persists, replace the device.
Table 5-2. Interpreting PlantWeb
™
Statuses
PlantWeb
status
Notification Description Recommended action(s)