Reference Manual
24
Reference Manual
00809-0100-4045, Rev AB
Configuration
March 2016
Configuration
See Local device status and notifications for more information.
From the HOME screen, enter the Fast Key sequence
1. From the Home screen, select 2: Configure
2. Select 2: Advance Setup
3. Select 1: Measurements
4. Select 1: Dial/Pressure
5. Select 3: Over-Press Ind
6. Follow the commands to perform the procedure.
Note
When the parameter has been set to activate, the notification must be acknowledged and
cleared for the device to return to normal operation.
Measured process
pressure
Parameter Configuration
Unlatched (factory default) Latched
>105% MWP
LED Color: Green
Dial Location: Off-scale
LED Color: Red
Dial Location: Red X
Fast Keys
2, 2, 1, 1, 3
Table 3-3. Dial Locations