Reference Manual

22
Reference Manual
00809-0100-4045, Rev AB
Configuration
March 2016
Configuration
Note
The following parameters pertaining to the device can be simulated:
Pressure, Sensor Temperature, and Supply Voltage
3.8.2 Device reset
The master reset function will reset the device electronics. To perform a device reset:
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 3: Service Tools.
2. Select 4: Maintenance
3. Select 1: Device Reset
3.8.3 Join status
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 3: Service Tools.
2. Select 3: Communications.
3. Select 1: Join Status.
Wireless devices join the secure network through a four-step process:
Step 1. Network Found
Step 2. Network Security Clearance Granted
Step 3. Network Bandwidth Allocated
Step 4. Network Join Complete
3.9 Advanced configuration
3.9.1 Overpressure notification
This notification can be used to know if a process pressure higher than 105% of the devices
maximum working pressure (MWP) has been measured. The overpressure notification must
be configured to latched mode to activate the notification. If this event occurs when the
device is configured to latch the dial will be driven to the Red X and the LED will blink red.
Additionally, it is required to acknowledge and reset the overpressure notification after an
overpressure event before the dial can move back to an on-scale position.
Fast Keys
3, 4, 1
Fast Keys
3, 3, 1