Reference Manual

20
Reference Manual
00809-0100-4045, Rev AB
Configuration
March 2016
Configuration
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 3: Service Tools.
2. Select 2: Variables.
The Operating Parameters menu displays the following information pertaining to the device:
Mapped Variables
- Primary Variable
- Secondary Variable
- Tertiary Variable
- Quaternary Variable
All Variables
- Pressure
- Pressure Quality
- Custom Scale
- Cust Scale Quality
- Percent of Range
- Percent of Rng Quality
- Sensor Temp
- Sensor Temp Quality
- Supply Voltage
- Supply Voltage Quality
3.7 Advanced device parameter setup
3.7.1 Write protect
The device has a software write protect security feature.
From the HOME screen, enter the Fast Key sequence.
1. Select Write Protect to enable.
2. Right click on device and select 2: Configure.
3. Select 2: Advanced Setup.
4. Select the tab labeled 4: Security.
5. Select Write Protect to enable this feature.
Fast Keys
3, 2
Fast Keys
2, 2, 4, 1