Reference Manual
19
Reference Manual
00809-0100-4045, Rev AB
Configuration
March 2016
Configuration
3.6.2 Review device information
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 1: Overview.
2. Select 9: Device Information.
3. Select from the corresponding number to view each field:
3.6.3 Review radio information
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 1: Overview.
2. Select 9: Device Information.
3. Select 3: Radio.
4. Select from the corresponding number to view each field:
3.6.4 Review operating parameters
The pressure output value in both engineering units and percent of range will reflect the
applied pressure even when the applied pressure is outside of the configured range as long
as the applied pressure is between the upper and lower range limit of the device. For
example, if a scale range 0 - 150 psi (LRL = 0 psi, URL = 150 psi) is ranged from 0 to 100 psi,
an applied pressure of 150 psi will return a % of range output of 150%.
Fast Keys
1, 9
1 Identification
2 Revisions
3 Radio
4 Materials of Construction
5 Security
6 Dial Faceplate
7 Capabilities
Fast Keys
1, 9, 3
1 MAC Address
2 Manufacturer
3 Device Type
4 Device Revision
5 Software Revision
6 Hardware Revision
7 Xmit Power Level
8 Min Brdcst Rate