Reference Manual
18
Reference Manual
00809-0100-4045, Rev AB
Configuration
March 2016
Configuration
Note
Joining the device to the network could take several minutes.
3.5.3 Considerations for devices with percent of range
engineering unit
Set range points
The range values command sets the lower and upper range values used for the percent of
range engineering unit.
Note
Devices are shipped from Emerson fully calibrated to the factory default of full scale (scale
range = upper range limit).
From the HOME screen, enter the Fast Key sequence.
1. Select lower or upper range value as applicable.
2. Follow the commands to perform the procedure.
3.6 Configuration verification
The following is a list of factory default configurations that can be viewed by using the Field
Communicator or AMS Device Manager. Follow the steps below to review the gauge
configuration information.
Note
Information and procedures in this section that make use of Field Communicator Fast Key
sequences and AMS Device Manager assume the gauge and communication equipment are
connected, powered, and operating correctly.
3.6.1 Review pressure information
From the HOME screen, enter the Fast Key sequence.
1. From the Home screen, select 1: Overview.
2. Select 3: Pressure.
Fast Keys
2, 2, 1, 2
Fast Keys
1, 3