00825-0200-4420_RevFD.
00825-0200-4420_RevFD.fm Page 2 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide NOTICE This guide provides basic guidelines for the Smart Wireless Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Smart Wireless Gateway Reference Manual (document number 00809-0200-4420) for more information and instructions. The manual and this Quick Start Guide are available electronically on www.emersonprocess.com.
00825-0200-4420_RevFD.fm Page 3 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Wireless considerations Power up sequence The Smart Wireless Gateway (Gateway) should be installed and functioning properly before power modules are installed in any wireless field devices. Wireless field devices should also be powered up in order of proximity from the Smart Wireless Gateway beginning with the closest. This will result in a simpler and faster network installation.
00825-0200-4420_RevFD.
00825-0200-4420_RevFD.fm Page 5 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Step 1: Initial connection and configuration DeltaV™ ready If the Gateway was ordered DeltaV Ready (Data Protocols Code 5), then Step 1: Initial connection and configuration is not required. Proceed to Step 2: Physical installation, and connect the Gateway to a DeltaV 10.3 or newer control network.
00825-0200-4420_RevFD.fm Page 6 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Note Figure 1 depicts the terminal block of legacy gateways prior to the introduction of PoE capabilities. Figure 2 shows the terminal block arrangement of a PoE version of the gateway. If the gateway will be powered via the standard 24 volt power input terminals, and no PSE is desired, it is not necessary to change the default settings of the PoE jumper matrix.
00825-0200-4420_RevFD.fm Page 7 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Note Only one port and one mode of operation (PD or PSE) can be selected at a time; any other combination of jumpers is invalid. Note IEEE 802.3af-2003 PoE standard provides up to 15.4 W of DC power (minimum 44 V DC and 350 mA) to each device. Only 12.95 W is assured to be available at the powered device as some power is dissipated in the cable. IEEE 802.
00825-0200-4420_RevFD.fm Page 8 Thursday, May 7, 2015 8:26 AM Quick Start Guide c. May 2015 Select Internet Protocol (TCP/IP), then select the Properties button. Note If the PC/laptop is from another network, record the current IP address and other settings so the PC/laptop can be returned to the original network after the Gateway has been configured. d. Select the Use the following IP address button. e. In the IP address field, enter 192.168.1.12. f. In the Subnet mask field, enter 255.255.255.
00825-0200-4420_RevFD.fm Page 9 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Table 1. Default IP Addresses Gateway PC/laptop Ethernet 1 192.168.1.10 192.168.1.12 Ethernet 2 192.168.2.10 192.168.2.12 Ethernet 1 (DeltaV Ready) 10.5.255.254 10.5.255.200 Ethernet 2 (DeltaV Ready) 10.9.255.254 10.9.255.200 Table 2. Subnet Settings Subnet mask Default 255.255.255.0 DeltaV 255.254.0.0 3. Disable proxies. a.
00825-0200-4420_RevFD.fm Page 10 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Configure the Smart Wireless Gateway To complete initial configuration for the gateway: 1. Access the default web page for the Gateway at https://192.168.1.10. a. b. In the User name field, enter admin. In the Password field, enter default. Figure 5. Gateway Log In Screen 2. Navigate to System Settings>Gateway>Ethernet Communication to enter the Network Settings. a. b.
00825-0200-4420_RevFD.fm Page 11 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Step 2: Physical installation Pipe mount Tools needed: 2-in. (51 mm) mounting pipe or mast Two 5/16-in. (7,9 mm) u-bolts supplied with Gateway 1 /2-in. socket-head wrench For installing the Gateway in a pipe mount: 1. Insert one u-bolt around the pipe, through the top mounting holes of the Gateway enclosure, and through the washer plate. 2. Use a 1/2-in.
00825-0200-4420_RevFD.fm Page 12 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Remote antenna (optional) The remote antenna options provide flexibility for mounting the Gateway based on wireless connectivity, lightning protection, and current work practices. When installing remote mount antennas for the Smart Wireless Gateway, always use established safety procedures to avoid falling or contact with high-power electrical lines.
00825-0200-4420_RevFD.fm Page 13 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Figure 6. Installation of WL2/WN2 Option B C D A E F G G H A. Control Building B. Remote Antenna C. Cable D.Drip Loop E. Lightning Arrestor F. Gateway G. Ground H. Earth Installation of WL3/WL4 option (indoor to outdoor applications) 1. Mount the antenna on a 1.5-2 inch pipe mast using the supplied mounting equipment. 2. Mount the lightning arrestor near the building egress. 3.
00825-0200-4420_RevFD.fm Page 14 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Figure 7. Installation of WL3/WL4 Option B C A D E F G G H A. Control Building B. Remote Antenna C. Cable D. Drip Loop E. Lightning Arrestor F. Gateway G. Ground H. Earth Note: Weather proofing is required! The remote mount antenna kit includes coaxial sealant for the cable connections for the lightning arrestor, antenna, and Gateway.
00825-0200-4420_RevFD.fm Page 15 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Table 3. Remote Antenna Kit Options Kit option Antenna Cable 1 Cable 2 Lightning arrestor /2 Wavelength Dipole Omni-Directional +6 dB Gain 50 ft. (15,2 m) LMR-400 N/A Head mount, jack to plug Gas discharge tube 0.5 dB insertion loss 30 ft. (9,1 m) LMR-400 20 ft. (6,1 m) LMR-400 In-line, jack to jack Gas discharge tube 0.5 dB insertion loss 40 ft. (12,2 m) LMR-400 10 ft.
00825-0200-4420_RevFD.fm Page 16 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Step 3: Connect to the host system 1. Wire the Gateway’s Ethernet 1 (Primary) or Serial Output connection to the Host System Network or Serial I/O. 2. For Serial connections, connect A to A, B to B, making sure all terminations are clean and secured to avoid wiring connection problems. Figure 9.
00825-0200-4420_RevFD.fm Page 17 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Twisted shielded pair cable is generally used to wire the Serial connection, and it is standard practice to ground the shield on the Serial Host side leaving the shield floating on the Gateway side. To avoid grounding issues be sure to insulate the shield. Power Power the gateway as directed in Step 1.
00825-0200-4420_RevFD.fm Page 18 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Step 5: Verify operations Operation is verified through the web interface by opening a web browser from any PC on the host system network and entering the Gateway IP address or DHCP host name in the address bar. If the Gateway has been connected and configured properly, the Security Alert will be displayed followed by the log in screen. Figure 11.
00825-0200-4420_RevFD.fm Page 19 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Product specifications Input power 10.5 – 30 VDC (must be a Class 2 power supply) Current draw Operating current draw is based on 3.6 W average power consumption. Momentary startup current draw up to twice operating current draw. Current (mA) Maximum permissible current: 1A Operating region Voltage (VDC) PoE(1) Input voltage Normal Operation (no PSE or IEEE 802.3af): 10.
00825-0200-4420_RevFD.fm Page 20 Thursday, May 7, 2015 8:26 AM Quick Start Guide Environmental Operating temperature range -40 to 140 °F (-40 to 70 °C) Operating humidity range 10-90% relative humidity Physical specifications Weight 10 lb (4.
00825-0200-4420_RevFD.fm Page 21 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Ethernet 10/1000base- TXEthernet communication port Protocols: Ethernet/IP ModbusTCP, OPC, HART-IP, HTTPS (for Web Interface) Wiring: Cat5Eshielded cable Wiring distance: 328 ft. (100 m) Modbus Supports Modbus RTU and Modbus TCP with 32-bit floating point values, integers, and scaled integers. Modbus Registers are user-specified.
00825-0200-4420_RevFD.fm Page 22 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Product Certifications Rev 1.1 European Directive Information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at www.rosemount.com. Telecommunication Compliance All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum.
00825-0200-4420_RevFD.fm Page 23 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Canada N6 Canada Division 2 Certificate: CSA 70010780 Standards: CAN/CSA C22.2 No. 0-M91 (R2001), CAN/CSA Std C22.2 No. 94-M91 (R2001), CSA Std C22.2 No. 142-M1987, CSA Std C22.2 No. 213-M1987, CSA C22.2 No. 61010-1 - 2012 Markings: Suitable for Class 1, Division 2, Groups A, B, C, and D, T4; when connected per Rosemount drawing 01420-1011; Type 4X Special Conditions for Safe Use: 1. Explosion Hazard.
00825-0200-4420_RevFD.fm Page 24 Thursday, May 7, 2015 8:26 AM Quick Start Guide May 2015 Special Condition for Safe Use (X): 1. The surface resistivity of the antenna is greater than 1GΩ. To avoid electrostatic charge build-up, it must not be rubbed with a dry cloth or cleaned with solvents. Brazil N2 INMETRO Type n Certificate: CEPEL 09.1844X Standards: ABNT NBR IEC 60079-0:2008, IEC 60079-15:2010, ABNT NBR IEC 60529:2009; Markings: Ex nA nL IIC T4 Gc Special Condition for Safe Use (X): 1.
00825-0200-4420_RevFD.fm Page 25 Thursday, May 7, 2015 8:26 AM May 2015 Quick Start Guide Figure 12.
00825-0200-4420_RevFD.
00825-0200-4420_RevFD.
00825-0200-4420_RevFD.fm Page 28 Thursday, May 7, 2015 8:26 AM *00825-0200-4420* Quick Start Guide 00825-0200-4420, Rev FD May 2015 Global Headquarters Emerson Process Management 6021 Innovation Blvd Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@EmersonProcess.com North America Regional Office Emerson Process Management 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.