Product specifications
60
Reference Manual
00809-0200-4420, Rev HB
Appendix B: Product Certifications
January 2015
Product Certifications
North America
N5 FM Division 2, Non-Incendive
Certificate: 3028321
Nonincendive for Class I, Division 2, Groups A, B, C, and D.
Suitable for Class II, III, Division 2, Groups E, F, and G.
Enclosure Type 4X
Temperature Code: T4 (-40 °C ≤ T
a
≤ 60 °C)
Canadian Standards Association (CSA)
N6 CSA Division 2
Certificate: 1849337
Suitable for Class I, Division 2, Groups A, B, C, and D.
Install per Rosemount drawing 01420-1011.
Temperature Code: T4 (-40 °C ≤ T
a
≤ 60 °C)
CSA Enclosure Type 4X
B.5 European Union Directive Information
The EC declaration of conformity for all applicable European directives for this product can be
found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by
contacting your local sales representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Emerson Process Management complies with the EMC Directive.
Radio and Telecommunications Terminal Equipment Directive (R&TTE)(1999/5/EC)
Emerson Process Management complies with the R&TTE Directive
Europe
N1 ATEX Type n
Certificate: Baseefa 07ATEX0056X
ATEX Marking: II 3 G
Ex nA nL IIC T4 (-40 °C ≤ T
a
≤ 60 °C)
Special Conditions for Safe Use (X):
1. The surface resistivity of the antenna is greater than one gigaohm. To avoid
electrostatic charge build-up, it must not be rubbed or cleaned with solvents or a dry
cloth.
2. The Apparatus is not capable of withstanding the 500V insulation test required by
Clause 9.4 of EN 60079-15: 2005. This must be taken into account when installing the
apparatus.