Product specifications

17
Reference Manual
00809-0200-4420, Rev HB
Section 3: Mounting and Connection
January 2015
Mounting and Connection
Figure 3-3. Installation of WL2/WN2 Option
Installation of WL3/WL4 Option (indoor to outdoor
applications)
1. Mount the antenna on a 1.5-2 inch pipe mast using the supplied mounting equipment.
2. Mount the lightning arrestor near the building egress.
3. Install the grounding lug, lock washer, and nut on top of lightning arrestor.
4. Connect the antenna to the lightning arrestor using the supplied coaxial cable ensuring
the drip loop is not closer than 1 foot (0,3 m) from the lightning arrestor.
5. Connect the lightning arrestor to the Gateway using the supplied coaxial cable.
6. Use the coaxial sealant to seal each connection between the Gateway, lightning
arrestor, cable, and antenna.
7. Ensure that the mounting mast, lightning arrestor, and Gateway are grounded
according to local/national electrical codes.
Note
Any spare lengths of coaxial cable should be placed in 12 inch (0,3 m) coils.
A. Control Building
B. Remote Antenna
C. Cable
D. Drip Loop
E. Lightning Arrestor
F. Gateway
G. Ground
H. Earth
B
C
D
E
F
A
G
H
G