Reference Manual

Reference Manual
00809-0100-4102, Rev AA
Section5:Operationand Maintenance
May 2013
Operation and maintenance
81
c o n
f
g
f
a
i
l
u
r
D i a g n o st i c Bu t t o n S c r e en 9 .1 :
configuration of the transmitter is
invalid such that critical operation
of the device may be affected -
check the extended configuration
status to identify which
configuration item(s) need to be
corrected
r
a d i o
f
a i
l
u
r
Di ag no st i c But to n Sc re e n 8 : t he
device may not be able to
communicate with the radio or
the radio has an internal error. In
this state the device may still be
operational and publishing HART
data
s u p
l
y
l
o
w
D i a g n o s ti c B u t t o n S c r e e n 7. 2 : t h e
terminal voltage is below the
recommended operating range -
the Power Module should be
replaced
s u p
l
y
f
a
i
l
u
r
D i a g n o s ti c B u t t o n S c r e e n 7. 1 : t h e
terminal voltage has dropped
below level of operating limit.
Replace the Power Module
(Part Number: 701PGNKF)